目的:了解佛山市部分公共场所集中式空调通风系统军团菌的污染状况及血清型别分布,为军团菌病的预防控制提供依据。方法:采集我市商场(超市)、宾馆及体育场馆共30家公共场所的集中式空调系统循环使用的冷却水和冷凝水共106份,分别进行军团菌的病原学调查。结果:106份水样中有54份检出军团菌,阳性率50.94%(54/106),并分离出62株军团菌,同一份水样同时检出两种不同血清型军团菌的占检出水样的14.81%(8/54),其中以嗜肺军团菌1型(LP1)为主,占58.06%(36/62)。结论:我市部分公共场所集中式空调通风系统军团菌污染较严重,对人群健康构成潜在的危害,应加强公共场所集中式空调通风系统的卫生监测。
Objective: To understand the pollution status and serotype distribution of Legionella in the centralized air-conditioning and ventilation system in some public places in Foshan City, and provide the basis for the prevention and control of Legionnaires’ disease. Methods: A total of 106 circulating cooling water and condensate water were collected from central air-conditioning system of 30 public places in our city shopping malls (supermarkets), hotels and stadiums, and the etiological investigation of Legionella was conducted respectively. Results: Legionella was detected in 54 out of 106 samples, with a positive rate of 50.94% (54/106). Legionella were isolated from 62 strains of Legionella and two different serotypes of Legionella were detected in the same sample The effluent samples were 14.81% (8/54), of which Legionella pneumophila type 1 (LP1) accounted for 58.06% (36/62). Conclusion: The Legionella bacteria in the centralized air-conditioning and ventilation system in some public places in our city are seriously polluted, posing a potential hazard to the health of the population. Health monitoring of the centralized air-conditioning and ventilation system in public places should be strengthened.