论文部分内容阅读
摘要:随着经济的迅速发展以及科学技术水平的不断提高,我国的电力工业取得了较大的进步。我们的研究课题是:水电站复杂厂用电保护整定值配合研究。首先主要针对某水电站的复杂厂进行一定程度上的研究,因为这一水电站复杂厂采用了较多数量的微机保护装置,因此进行对其运行方式的分析存在一定的难度。对于这一问题,我们通过对电场的实际运行的工况进行结合,并相应的提出了从厂用电母线开始研究,以实现对于母线的最大运行方式以及最小运行方式的确定。然后,以此为基础,对复杂系统整定值配合的问题进行研究与分析。这样一来,就能够对复杂厂用电系统多级保护之间保护动作时间的配合问题进行有效的解决。
关键词:水电站;厂用电;保护整定;运行方式;时间级差
Abstract: with the rapid development of economy and the improvement of science and technology, our power industry has made great progress. We research is: hydropower station, the complex power protection setting value with research. First in a major hydropower station to a certain extent the complex of research because the hydropower station with more complex factory number of microcomputer protection device, so on the analysis of the operation modes there are some difficulties. For this problem, we through to the actual operation of electric field of working condition combination, and corresponding proposed from the bus began to study power plant, in order to realize the biggest operation mode for bus and the determination of minimum operation mode. And then, based on this, the set values for complex system with the problem of research and analysis. In this way, can the power system of complex multistage protection to protect the action time between the match problem effectively solved.
Keywords: hydropower station; Factory electricity; Protection setting; Operation mode; Differential time
中图分类号:[TM622]文献标识码:A 文章编号:
1.引言
近几年来,我国的电力工业取得了很大的发展,与之相关的设施也逐步升级与完善,尤其是表现在大型发电厂的单机之上。随着相关技术的不断升级与发展,其容量日益增大,在数量上也日益增多。因此,对厂用电供电提出了更高的要求,要求其在可靠程度以及灵活程度方面都需得到一定程度的保证。目前状况下,所采用的方法是设置大量的厂用电电源以及供电点来实现对其可靠性以及灵活性的保证。这样一来,就增加了其运行方式以及系统接线的复杂程度,对继电保护
的整定以及保护定值的配合造成一定的影响。
2.最大、最小运行方式的分析
对于最大、最小运行方式来说,它主要指的是相关的系统在这种运行方式之下,所具有的最大、最小的短路阻抗值,当发生短路之后会产生相应的短路电流最大、最小的一种运行方式。然而,这一定义在保护整定以及校验多级多母线系统方面却不是完全的适合。主要原因是当相关系统存在着较多的母线之时,就不能对短路后其电流值是否能达到最大、最小进行保证。所以,如果运用系统的最大、最小的运行方式来进行相应的保护整定以及校检工作,会促使所得出来的值与实际值误差较大,从而进一步引起一定程度上的保护误动或者保护拒动。
而如果从母线进行相关的研究与分析,并对其最大、最小运行方式进行确定,就可以对上述问题进行准确而有效的解决。下面我们对其方法进行阐述:首先,一般情况下,母线会存在着多种运行方式,需要对其可能的运行方式进行列举。同时,在其母线处进行三相短路故障的设置。以此实现一定程度上的仿真计算。这样一来,就可以根据电流值最大、最小的运行方式来对母线运行方式进行判断。
根据电厂厂用电的相关规程,我们进行了辅助供电系统的运行方式的列举,然后在这一基础之上进行相应的仿真计算。依据计算结果,确定了它的最大运行方式——单机双变以及最小运行方式——电源电站孤网运行。
3.保护整定及定值配合
目前状况下,该水电厂仍然运用传统方法来是实现用电保护,也就是三段式电流保护。对于保护定值的配合来说,它主要包含了两个部分,分别是电流元件定值的配合以及动作时间的配合。根据相关原则规定,电流元件定值的配合与动作时间的配合分别通过可靠系数以及時间极差来对其进行一定程度上的保证。而实际情况是,该水电厂的厂用电系统复杂程度较高,这就给保护定值的配合带来困难,出现了一系列的问题。
3.1 馈线保护整定以及定值配合
对于短路电流的计算,首先需要进行对于三相短路故障的设置,设置点主要是在变压器的高压侧以及低压侧,然后再进行对于短路电流的计算。
对于无时限电流速断保护的整定主要是通过按照最大方式下相关线路的末端所发生的三相短路来进行的。相关的计算结果表明:因为10kv的馈线没有达到足够的长度,无时限电流速断并没不存在相应的保护范围,所以通常情况下将几个线路看作为一个线路变压器组。也就是说将其视为一个整体部分来进行保护,整定的计算公式主要如下:
IOP=KrIk,max
描述:在上一式子中,Kr主要指的是可靠系数,其取值一般在1.3到1.4的范围之内。然而在本次的整定操作之中,相关电源的运行方式发生了较大程度上的变化,所以对其可靠系数进行一定程度上的降低,取值为1.2;而Ik,max主要指的是在最大运行方式之下,相关变压器的低压侧的三相短路的电流。进行灵敏度的校验主要采取以下的近似公式:
描述:在如上显示的近似公式当中,Is,max主要指的是系统的最大的等值电抗;而XT一级Z1分别指的是保护变压器的电抗以及保护线路的阻抗。而因为相关变压器的电抗与线路的阻抗相比,其值过大,因此,在实际情况中,无时限电流速断保护能够对线路的全长进行一定程度上的保护,保护的延长时间为0。
定时限过电流保护整定的公式主要如下:
描述:Ks主要指的是自启动系数,一般情况下,主要是根据负荷的性质对其的取值进行确定。
该水电厂的各个馈线变压器都存在着较多的负荷,这样一来,进行对于负荷性质的精确统计就存在较大程度上的困难。在对Ks进行确定时,选择该厂具有典型性的馈线变压器进行研究与分析。在相关的统计之中,旋转的负荷大约占到额定负荷的65%,再将65%与7的乘积加上35%與1的乘积,得到结果4.9,由此可知,综合自启动系数的值只要取5就可以达到相应的标准。
3.2 进线、联络线保护整定以及定值配合
在进行整定计算之时,我们有如下发现:因为10kv的进线、联络线的长度不够,而且短路电流的曲线也太过平整,这样一来就在一定程度上的导致了无时限电流速断保护不存在相应的保护范围。所以,10kv进线、联络线只能配置限时电流速断保护以及相应的定时限过电流保护,为了对其保护的速动性进行一定程度上的保证,需要尽量压缩限时电流速断保护的延长时间。
一般情况下,对于限时电流速断的整定需要遵循一定的原则:要求限时电流速断保护需要与下一级馈线的无时限电流速断保护达到一定程度上的配合,将Kr取值为1.5。然而,如果按照这一原则进行对于整定时,有可能会出现定
时限过电流保护定值与限时电流速断保护定值相比略大的情况,这样就不能够达到相关的要求。所以,首先对其灵敏度进行保证,然后在一定程度上进行对于限时电流速断保护的整定值的提高。
4.结束语
本文主要针对水电站复杂厂用电保护整定值配合进行了研究与分析,先从其最大、最小运行方式方面开展分析,确定了该厂辅助供电系统的最大运行方式以及最小运行方式。然后,从馈线保护整定以及定值配合以及进线、联络线保护整定以及定值配合两个方面分析了保护整定及定值配合。希望我们的研究可以为读者带来帮助。
参考文献:
[1]易亚文,易娜.复杂厂用电系统继电保护定值配合[J]. 水电自动化与大坝监测,2009,33(4):31-34.
[2]DL/T584-2007 3kV-110kV电网继电保护装置运行整定规程[S].北京:中国电力出版社,2008.
[3]GB/T14285-2006继电保护和安全自动装置技术规程[S].北京:中国标准出版社,2006.
[4]常凤然,周纪录.缩短继电保护时间级差的分析[J].河北电力技术,1998,17(4):56-57.
[5]易亚文,易娜.复杂厂用电系统继电保护定值配合[J].水电自动化与大坝监测,2009,(04).
[6]常凤然,周纪录,张洪,于全党. 缩短继电保护时间级差的分析[J].河北电力技术,1998,(04).
[7]华东电力设计院,华北电力设计院,东北电力设计院.GB/T14285-2006继电保护和安全自动装置技术规程[S].,2006.
[8]王薇.一起系统复杂故障状态下保护动作分析[J].安徽电气工程职业技术学院学报, 2009,(03).
[9]唐俊,张鲁.220kVUFV-200J型备自投装置在西梁山变电站的应用分析[J].安徽电气工程职业技术学院学报, 2010,(03).
[10]方学霞.华电芜湖电厂启备变保护电流互感器的配置与选型[J].安徽电气工程职业技术学院学报,2010,(03).
关键词:水电站;厂用电;保护整定;运行方式;时间级差
Abstract: with the rapid development of economy and the improvement of science and technology, our power industry has made great progress. We research is: hydropower station, the complex power protection setting value with research. First in a major hydropower station to a certain extent the complex of research because the hydropower station with more complex factory number of microcomputer protection device, so on the analysis of the operation modes there are some difficulties. For this problem, we through to the actual operation of electric field of working condition combination, and corresponding proposed from the bus began to study power plant, in order to realize the biggest operation mode for bus and the determination of minimum operation mode. And then, based on this, the set values for complex system with the problem of research and analysis. In this way, can the power system of complex multistage protection to protect the action time between the match problem effectively solved.
Keywords: hydropower station; Factory electricity; Protection setting; Operation mode; Differential time
中图分类号:[TM622]文献标识码:A 文章编号:
1.引言
近几年来,我国的电力工业取得了很大的发展,与之相关的设施也逐步升级与完善,尤其是表现在大型发电厂的单机之上。随着相关技术的不断升级与发展,其容量日益增大,在数量上也日益增多。因此,对厂用电供电提出了更高的要求,要求其在可靠程度以及灵活程度方面都需得到一定程度的保证。目前状况下,所采用的方法是设置大量的厂用电电源以及供电点来实现对其可靠性以及灵活性的保证。这样一来,就增加了其运行方式以及系统接线的复杂程度,对继电保护
的整定以及保护定值的配合造成一定的影响。
2.最大、最小运行方式的分析
对于最大、最小运行方式来说,它主要指的是相关的系统在这种运行方式之下,所具有的最大、最小的短路阻抗值,当发生短路之后会产生相应的短路电流最大、最小的一种运行方式。然而,这一定义在保护整定以及校验多级多母线系统方面却不是完全的适合。主要原因是当相关系统存在着较多的母线之时,就不能对短路后其电流值是否能达到最大、最小进行保证。所以,如果运用系统的最大、最小的运行方式来进行相应的保护整定以及校检工作,会促使所得出来的值与实际值误差较大,从而进一步引起一定程度上的保护误动或者保护拒动。
而如果从母线进行相关的研究与分析,并对其最大、最小运行方式进行确定,就可以对上述问题进行准确而有效的解决。下面我们对其方法进行阐述:首先,一般情况下,母线会存在着多种运行方式,需要对其可能的运行方式进行列举。同时,在其母线处进行三相短路故障的设置。以此实现一定程度上的仿真计算。这样一来,就可以根据电流值最大、最小的运行方式来对母线运行方式进行判断。
根据电厂厂用电的相关规程,我们进行了辅助供电系统的运行方式的列举,然后在这一基础之上进行相应的仿真计算。依据计算结果,确定了它的最大运行方式——单机双变以及最小运行方式——电源电站孤网运行。
3.保护整定及定值配合
目前状况下,该水电厂仍然运用传统方法来是实现用电保护,也就是三段式电流保护。对于保护定值的配合来说,它主要包含了两个部分,分别是电流元件定值的配合以及动作时间的配合。根据相关原则规定,电流元件定值的配合与动作时间的配合分别通过可靠系数以及時间极差来对其进行一定程度上的保证。而实际情况是,该水电厂的厂用电系统复杂程度较高,这就给保护定值的配合带来困难,出现了一系列的问题。
3.1 馈线保护整定以及定值配合
对于短路电流的计算,首先需要进行对于三相短路故障的设置,设置点主要是在变压器的高压侧以及低压侧,然后再进行对于短路电流的计算。
对于无时限电流速断保护的整定主要是通过按照最大方式下相关线路的末端所发生的三相短路来进行的。相关的计算结果表明:因为10kv的馈线没有达到足够的长度,无时限电流速断并没不存在相应的保护范围,所以通常情况下将几个线路看作为一个线路变压器组。也就是说将其视为一个整体部分来进行保护,整定的计算公式主要如下:
IOP=KrIk,max
描述:在上一式子中,Kr主要指的是可靠系数,其取值一般在1.3到1.4的范围之内。然而在本次的整定操作之中,相关电源的运行方式发生了较大程度上的变化,所以对其可靠系数进行一定程度上的降低,取值为1.2;而Ik,max主要指的是在最大运行方式之下,相关变压器的低压侧的三相短路的电流。进行灵敏度的校验主要采取以下的近似公式:
描述:在如上显示的近似公式当中,Is,max主要指的是系统的最大的等值电抗;而XT一级Z1分别指的是保护变压器的电抗以及保护线路的阻抗。而因为相关变压器的电抗与线路的阻抗相比,其值过大,因此,在实际情况中,无时限电流速断保护能够对线路的全长进行一定程度上的保护,保护的延长时间为0。
定时限过电流保护整定的公式主要如下:
描述:Ks主要指的是自启动系数,一般情况下,主要是根据负荷的性质对其的取值进行确定。
该水电厂的各个馈线变压器都存在着较多的负荷,这样一来,进行对于负荷性质的精确统计就存在较大程度上的困难。在对Ks进行确定时,选择该厂具有典型性的馈线变压器进行研究与分析。在相关的统计之中,旋转的负荷大约占到额定负荷的65%,再将65%与7的乘积加上35%與1的乘积,得到结果4.9,由此可知,综合自启动系数的值只要取5就可以达到相应的标准。
3.2 进线、联络线保护整定以及定值配合
在进行整定计算之时,我们有如下发现:因为10kv的进线、联络线的长度不够,而且短路电流的曲线也太过平整,这样一来就在一定程度上的导致了无时限电流速断保护不存在相应的保护范围。所以,10kv进线、联络线只能配置限时电流速断保护以及相应的定时限过电流保护,为了对其保护的速动性进行一定程度上的保证,需要尽量压缩限时电流速断保护的延长时间。
一般情况下,对于限时电流速断的整定需要遵循一定的原则:要求限时电流速断保护需要与下一级馈线的无时限电流速断保护达到一定程度上的配合,将Kr取值为1.5。然而,如果按照这一原则进行对于整定时,有可能会出现定
时限过电流保护定值与限时电流速断保护定值相比略大的情况,这样就不能够达到相关的要求。所以,首先对其灵敏度进行保证,然后在一定程度上进行对于限时电流速断保护的整定值的提高。
4.结束语
本文主要针对水电站复杂厂用电保护整定值配合进行了研究与分析,先从其最大、最小运行方式方面开展分析,确定了该厂辅助供电系统的最大运行方式以及最小运行方式。然后,从馈线保护整定以及定值配合以及进线、联络线保护整定以及定值配合两个方面分析了保护整定及定值配合。希望我们的研究可以为读者带来帮助。
参考文献:
[1]易亚文,易娜.复杂厂用电系统继电保护定值配合[J]. 水电自动化与大坝监测,2009,33(4):31-34.
[2]DL/T584-2007 3kV-110kV电网继电保护装置运行整定规程[S].北京:中国电力出版社,2008.
[3]GB/T14285-2006继电保护和安全自动装置技术规程[S].北京:中国标准出版社,2006.
[4]常凤然,周纪录.缩短继电保护时间级差的分析[J].河北电力技术,1998,17(4):56-57.
[5]易亚文,易娜.复杂厂用电系统继电保护定值配合[J].水电自动化与大坝监测,2009,(04).
[6]常凤然,周纪录,张洪,于全党. 缩短继电保护时间级差的分析[J].河北电力技术,1998,(04).
[7]华东电力设计院,华北电力设计院,东北电力设计院.GB/T14285-2006继电保护和安全自动装置技术规程[S].,2006.
[8]王薇.一起系统复杂故障状态下保护动作分析[J].安徽电气工程职业技术学院学报, 2009,(03).
[9]唐俊,张鲁.220kVUFV-200J型备自投装置在西梁山变电站的应用分析[J].安徽电气工程职业技术学院学报, 2010,(03).
[10]方学霞.华电芜湖电厂启备变保护电流互感器的配置与选型[J].安徽电气工程职业技术学院学报,2010,(03).