【摘 要】三相电力电缆的接地故障(单相、两相或三相接地)在电力系统中属于常见故障。如何快速检测处理电缆的接地故障点(尤其是直埋电缆的接地故障),确保电力电缆在电力系统中的正常运行,成为目前值得探讨的一个理论课题。在新丰电厂2×300MW机组工程的实践过程中,我们利用小电流检测动力电缆的接地故障点,即对故障接地的缆芯或电缆通过一定的阻值施加一个恒定的电流(5A~10A),然后用钳型电流表分点检测缆芯或电缆有无电流。有电流和无电流之间的区域即为接地故障点区域,逐步缩小测量范围,就能很快找到故障点。
【关键词】小电流;检测;动力电缆;接地故障点
Small current detection using ground power cable fault
Liu Jun-feng
(Shanxi Electric Power Company to build three companies Taiyuan Shanxi 030000)
【Abstract】Three-phase power cable ground fault (single-phase, two phase or three-phase ground) are common in power system failures. How to deal with rapid detection of the ground cable fault (especially the ground fault buried cable), ensure that the power cable in the power system normal operation, become the subject of a theory worth exploring. In the Xinfeng Power Plant 2 × 300MW units engineering practice, we use low current power cable ground fault detection point, that is grounded on the failure or cable through the cable core to exert a certain resistance constant current (5A ~ 10A ), then use the clamp-type ammeter test points or cable without the cable core current. There are no current between the current and the area is the ground fault zone, gradually narrow the range, you can quickly find the point of failure.
【Key words】Small current;Detection;Power cable;Ground fault
1. 三相电力电缆接地故障(单相、两相或三相接地)是电力系统运行中的常见故障。
快速检测电缆的接地故障点是一项比较困难的工作,尤其是直埋电缆接地故障点的检测。如何快速检测处理电缆的接地故障点,确保电力电缆在电力系统中的正常运行,成为目前值得探讨的一个理论课题。
2. 电力电缆接地故障是指因缆芯对外皮或钢铠间的绝缘破坏形成的单相、两相或三相接地故障。
其中短路接地又有高阻和低阻之分,一般来说将接地电阻小于50Ω的接地故障称为低阻接地,接地电阻大于50Ω的接地故障称为高阻接地。
3. 目前,测量电缆接地故障点常用的方式主要有直流电桥法和脉冲法。
3.1 直流电桥法是基于电缆沿线均匀、电缆长度与缆芯电阻成正比的特点并根据惠斯通电桥的原理,将电缆短路接地故障点两侧的环线电阻引入直流电桥,测量其比值,由测得的比值和电缆的长度,可计算出测量端到故障点的距离。其接线如图1所示:
图1
3.2 脉冲法主要是通过向故障电缆发射脉冲的测距方法,可分为低压脉冲反射法和高压脉冲反射法。
3.3 以上两种方法在新丰电厂2×300MW机组工程的实践过程中,利用小电流检测动力电缆的接地故障点,特别是低阻接地的电缆故障,效果比较好。它是基于电缆故障点接地的特点,通过一个合适的负载给故障电缆施加一个合理的接地电流,然后根据电缆的长度选择一定数量的检测点,利用钳型电流表对故障电缆进行检测,在有电流和无电流的连续两点之间,即为电缆的故障区域,再使用相同的方式缩小故障区域,最后查找出电缆故障点。其接线如图2所示:
图2
如图2示,在故障电缆的一端通过电流发生器对有故障的缆芯施加一定的电流(电流的大小根据其接地阻值确定),然后将电缆分为a、b、c、d四个测试点,利用钳型电流表对故障电缆进行检测,可以检测出在b点有电流流过而在c点则没有电流,由此可以断定故障点就在b、c两点之间。将b、c两点再分为若干点进行测试,则可以迅速把故障点缩小到一定的范围之内,以便尽快消除故障。这种方式对于低阻接地的电缆故障,效果很好。尤其是对于直埋电缆,由于其敷设路径的不确定性,采用直流电桥法和脉冲法不方便时,此种方法更显示出简单方便、快速有效的特点。
对于低阻接地的电缆故障,尤其是直埋电缆的低阻接地故障,在没有电流发生器等试验仪器的情况下,也可以在故障电缆的一端连接一个与接地电阻值相同的负载,然后加上220V交流电源,检测电缆的故障点。这种情况特别适用于电力建设施工单位在没有试验仪器的情况下,对低阻接地的故障电缆进行检测。
新丰电厂1#机组柴油发电机至事故保安段电源采用ZRC-VV22-3×185电力电缆。在柴油发电机安装调试过程中,电缆发生单相接地故障,停电后检测接地电阻只有2.3Ω。根据现场实际情况,在电缆的一端串接了一只1000W的电阻丝,然后通过电阻丝施加220V交流电源,利用钳型电流表对故障电缆进行检测,很快找到了电缆的接地故障点。
4. 通过上面的叙述,可以看出上述方法显然不适用于电缆的高阻接地故障。对于高阻接地故障使用何种简单有效的方法进行测试,还需要我们不断的进行探讨和研究。
[文章编号]1006-7619(2011)06-14-601
注:本文中所涉及到的图表、注解、公式等内容请以PDF格式阅读原文
【关键词】小电流;检测;动力电缆;接地故障点
Small current detection using ground power cable fault
Liu Jun-feng
(Shanxi Electric Power Company to build three companies Taiyuan Shanxi 030000)
【Abstract】Three-phase power cable ground fault (single-phase, two phase or three-phase ground) are common in power system failures. How to deal with rapid detection of the ground cable fault (especially the ground fault buried cable), ensure that the power cable in the power system normal operation, become the subject of a theory worth exploring. In the Xinfeng Power Plant 2 × 300MW units engineering practice, we use low current power cable ground fault detection point, that is grounded on the failure or cable through the cable core to exert a certain resistance constant current (5A ~ 10A ), then use the clamp-type ammeter test points or cable without the cable core current. There are no current between the current and the area is the ground fault zone, gradually narrow the range, you can quickly find the point of failure.
【Key words】Small current;Detection;Power cable;Ground fault
1. 三相电力电缆接地故障(单相、两相或三相接地)是电力系统运行中的常见故障。
快速检测电缆的接地故障点是一项比较困难的工作,尤其是直埋电缆接地故障点的检测。如何快速检测处理电缆的接地故障点,确保电力电缆在电力系统中的正常运行,成为目前值得探讨的一个理论课题。
2. 电力电缆接地故障是指因缆芯对外皮或钢铠间的绝缘破坏形成的单相、两相或三相接地故障。
其中短路接地又有高阻和低阻之分,一般来说将接地电阻小于50Ω的接地故障称为低阻接地,接地电阻大于50Ω的接地故障称为高阻接地。
3. 目前,测量电缆接地故障点常用的方式主要有直流电桥法和脉冲法。
3.1 直流电桥法是基于电缆沿线均匀、电缆长度与缆芯电阻成正比的特点并根据惠斯通电桥的原理,将电缆短路接地故障点两侧的环线电阻引入直流电桥,测量其比值,由测得的比值和电缆的长度,可计算出测量端到故障点的距离。其接线如图1所示:
图1
3.2 脉冲法主要是通过向故障电缆发射脉冲的测距方法,可分为低压脉冲反射法和高压脉冲反射法。
3.3 以上两种方法在新丰电厂2×300MW机组工程的实践过程中,利用小电流检测动力电缆的接地故障点,特别是低阻接地的电缆故障,效果比较好。它是基于电缆故障点接地的特点,通过一个合适的负载给故障电缆施加一个合理的接地电流,然后根据电缆的长度选择一定数量的检测点,利用钳型电流表对故障电缆进行检测,在有电流和无电流的连续两点之间,即为电缆的故障区域,再使用相同的方式缩小故障区域,最后查找出电缆故障点。其接线如图2所示:
图2
如图2示,在故障电缆的一端通过电流发生器对有故障的缆芯施加一定的电流(电流的大小根据其接地阻值确定),然后将电缆分为a、b、c、d四个测试点,利用钳型电流表对故障电缆进行检测,可以检测出在b点有电流流过而在c点则没有电流,由此可以断定故障点就在b、c两点之间。将b、c两点再分为若干点进行测试,则可以迅速把故障点缩小到一定的范围之内,以便尽快消除故障。这种方式对于低阻接地的电缆故障,效果很好。尤其是对于直埋电缆,由于其敷设路径的不确定性,采用直流电桥法和脉冲法不方便时,此种方法更显示出简单方便、快速有效的特点。
对于低阻接地的电缆故障,尤其是直埋电缆的低阻接地故障,在没有电流发生器等试验仪器的情况下,也可以在故障电缆的一端连接一个与接地电阻值相同的负载,然后加上220V交流电源,检测电缆的故障点。这种情况特别适用于电力建设施工单位在没有试验仪器的情况下,对低阻接地的故障电缆进行检测。
新丰电厂1#机组柴油发电机至事故保安段电源采用ZRC-VV22-3×185电力电缆。在柴油发电机安装调试过程中,电缆发生单相接地故障,停电后检测接地电阻只有2.3Ω。根据现场实际情况,在电缆的一端串接了一只1000W的电阻丝,然后通过电阻丝施加220V交流电源,利用钳型电流表对故障电缆进行检测,很快找到了电缆的接地故障点。
4. 通过上面的叙述,可以看出上述方法显然不适用于电缆的高阻接地故障。对于高阻接地故障使用何种简单有效的方法进行测试,还需要我们不断的进行探讨和研究。