我单位应用Windows 3.x下S900工控组态软件实施的高炉、焦炉煤气混合,配套设备的计算机集散控制系统,经过近一个月的无负荷运行和97年近一年的全负荷运行,实现了高、焦炉煤气混合的全自动配比,稳定了加压机前混合煤气的压力,保证了用户端混合煤压力的相对稳定,使输出煤气热值的稳定有了一定的可操作性。 该系统投入运行以来,一直运行良好,监视管理系统稳定可靠。但近一段时间,总是发生原因不明的死机现象,表现为时间标志停止,画面不动。仔细研究程序的初始化参数设置,没有异常。又一次系统调零时,遇到死机现象,仔细观察屏幕画面,发现时间参数停止,但Windows的Mouse光标似一直在闪烁,依次分析,好象显示器在进行画面切换,读取文件时,出现问题。于是用磁盘工具——
I use the unit under the Windows 3.x S900 industrial configuration software implementation of the blast furnace, coke oven gas mixture, supporting equipment, computer distributed control system, after nearly a month of no-load operation and 97 years of nearly a year of full-load operation to achieve High, coke oven gas mixture of the automatic ratio, stabilizing the pressure of the mixed gas before the press to ensure that the client side of the mixed coal pressure is relatively stable, the stability of the calorific value of the output gas has a certain maneuverability. Since the system was put into operation, it has been operating well and the monitoring management system has been stable and reliable. However, for some time now, unexplained crashes have always taken place, manifested as the stop of the time sign and the inactivity of the picture. Carefully study the initialization parameters of the program settings, there is no exception. Another system zero, encountered a crash, a careful observation of the screen and found that the time parameters to stop, but the Windows Mouse cursor has been flashing, followed by analysis, as if the monitor during the screen switch, read the file, there is a problem . So with the disk tool -