我厂生化脱酚工段废水循环槽高4M,在地面下有1.5M,其余在地面上(如图一所示)。为了测量液面变化,在地下阴井内接装了差压变送器,变送器之正压室与槽底部之静压引出管相接。用测量静压的大小来反映液位的变化,但因阴井潮湿,变送器不能正常工作,为此把变送器安装在地面上1米处。再用变送器迁移原理,同样达到了反映液面全程变化的要求。
I plant biochemical phenol removal section of the wastewater cycle tank high 4M, 1.5M under the ground, the rest on the ground (as shown in Figure 1). In order to measure the liquid level change, the differential pressure transmitter is installed in the underground shaft, and the positive pressure chamber of the transmitter is connected with the hydrostatic outlet pipe at the bottom of the tank. With the size of the measurement of static pressure to reflect changes in the level, but wet well, the transmitter does not work, for which the transmitter installed on the ground 1 meter. Then use the principle of transmitter migration, also reached the same level to reflect changes in the liquid requirements.