按照空气动力弹性相似准则 ,设计制作了某高压输电线路终端塔全塔气动弹性模型 ,并按响应相似原则模拟了柔性输电导线 ;在大气边界层风洞中进行了风荷载及风振响应的试验研究 ,获得了塔架体型系数、风振响应和风振系数等设计数据 ,并研究了输电导线对塔架风振的影响
According to the similarity criterion of aeroelasticity, the aeroelastic model of the terminal tower of a high voltage transmission line was designed and manufactured, and the flexible transmission line was simulated according to the principle of response similarity. The wind load and wind-induced vibration response were tested in the atmospheric boundary layer wind tunnel The design data such as tower body factor, wind-induced vibration response and wind-induced vibration coefficient were obtained. The influence of transmission conductors on tower wind-induced vibration was also studied