针对厂房溶液除湿空调系统中的回风处理系统——部分回风进除湿器,部分回风进表冷器的方案容易造成再生器过热,进而导致系统的除湿效率降低,除湿效果不明显,能耗增加等问题。本文提出先直接将回风全部进除湿器,然后再通过表冷器进行降温的优化方案,并通过实际测量,计算对比了两种系统的初投资及能耗,发现优化方案更加节能。
Aiming at the return air treatment system in the dehumidification air-conditioning system of the plant solution, part of the return air into the dehumidifier and part of the return air into the surface cooler can easily cause the regenerator to overheat, which leads to the decrease of the dehumidification efficiency of the system and the obvious effect of dehumidification. Consumption and other issues. In this paper, the optimization scheme of directly cooling the return air all the way to the dehumidifier and then the cooling by the surface cooler is proposed. The initial investment and energy consumption of the two systems are calculated and compared through actual measurement, and the optimal scheme is found to be more energy efficient.