远程控制终端阀室大多位置偏僻,特别是我国西部,昼夜温差较大,经常造成RTU阀室冬季温度过低。主要原因是阀室内没有足够热量,仅靠设备运行产生的热量,不足以维持PLC控制柜的最低运行温度,因此需要使用外供热源。在PLC控制柜底部安装两片30W加热片,RTU阀室温度明显提升,PLC控制柜内的温度由0℃左右提升至6℃。若将加热片数量增至10片,控制室的温度可以恒定在10℃,从而可以彻底消除PLC在低温下工作效率低、甚至停止工作的风险。
Remote control terminal valve room most of the remote location, especially in western China, a larger temperature difference between day and night, often causing RTU valve room temperature is too low in winter. The main reason is that there is not enough heat in the valve room and the heat generated by the operation of the equipment is not enough to maintain the minimum operating temperature of the PLC control cabinet. Therefore, the external heat source needs to be used. Installed in the PLC control cabinet at the bottom of two 30W heating film, RTU valve room temperature was significantly improved, PLC control cabinet temperature from 0 ℃ to 6 ℃. If the number of heating plates increased to 10, the control room temperature can be constant at 10 ℃, which can completely eliminate the PLC at low temperature work efficiency is low, or even stop working risk.