分析了混合型有源电力补偿技术的原理 ,提出了混合型有源补偿与常规并联有源滤波器在直流侧电容电压、装置容量等方面进行比较的分析方法。分析表明 ,混合型有源补偿具有直流侧电容电压低、在补偿同等容量负荷条件下其逆变器容量远小于常规有源滤波逆变器容量的突出优点。对两者所进行的计算机仿真结果与理论计算值相吻合。最后 ,文中给出了 5 0 k VA样机的实验结果 ,验证了混合型有源电力补偿技术具有良好的补偿特性
The principle of hybrid active power compensation technology is analyzed and the analytical method of hybrid active compensation and conventional shunt active power filter in the aspect of DC capacitor voltage and device capacity are proposed. The analysis shows that hybrid active compensation has the outstanding advantages of low DC-side capacitor voltage and much smaller inverter capacity than that of conventional active power inverter when the same capacity load is compensated. The results of computer simulation of the two agree well with the theoretical ones. Finally, the experimental results of a 50 kVA prototype are given, and the hybrid active power compensation technique is verified to have good compensation characteristics