摘要:随着中国经济的快速发展,建筑行业作为经济发展的中心被各级市政府所重视,随之而来的建筑设计质量也被各级审查部门所关注。本文主要通过对采暖设计中存在的集气、热网水平失调和垂直失调等问题进行分析,对通风设计中气流组织与风口布置、风管设计和风机选型中存在的一些问题进行分析,总结了一些设计中解决问题的方法。可供同行参考。
关键词: 采暖; 通风; 问题; 对策;
Abstract: Along with the rapid development of China's economy, construction industry as the center of the economic development by municipal government at all levels to subsequent construction design quality were also concerned examination department at all levels. This paper mainly through existing in the design of heating of gas, water level set disorder and vertical disorders and problems were analyzed, and the design of ventilation air distribution and draught layout, duct design and fan selection some problems in the analysis, summarizes some design methods to solve the problems. Available for reference to fellow.
Key Words: Heating; Ventilation; Problem; Countermeasures
中图分类号:S611 文献标识码:A 文章编号
前言
采暖、通风系统中出现的问题会影响系统的正常运行,通过对采暖设计中存在的集气、热网水平失调和垂直失调等问题进行分析,及对通风设计中气流组织与风口布置、风管设计和风机选型中存在的一些问题进行分析,总结了一些解决问题的方法,供在今后设计中参考。
一、采暖设计常见问题
采暖系统分为机械循环热水采暖系统和自然循环热水采暖系统。机械循环热水采暖系统是以水泵为循环动力,不受锅炉房位置高低及系统作用半径的限制,管中流速较大。系统所带的环路、支立管数较多,成为一个闭式的循环热水网,是一个复杂的水力系统。自然循环热水采暖系统是靠供、回水的密度差产生的作用压头克服系统阻力的,一般压头较小,管中流速一般较小。常采用异程式设计,易于平衡和调节。
1、集气、反坡和热负荷计算
一是供暖期间,个别房间散热器不热,其它房间散热器良好。房间立管、支管符合安装要求。原因分析:散热器内部集气。在热水系统中,空气是最有害的因素。在系统充水前存在的空气、通过不严密处渗入的空气、从水中分解出来的空气是热水供暖系统空气的主要来源。当管道中有空气积存时,往往会影响热水的正常循环。空气比水轻,空气都积存于系统的最高点,因此在采暖系统的设计中,一定要在系统的高处安装放气阀。对策:打开散热器的放气阀,直到有少量的水流出再关闭阀门。
二是用土暖气供暖,系统安装完后出现多种情况,如部分房间不热,打开散热器旁的放气阀,放出很多热蒸气,水箱在系统运行时不断的向外溢水,使地面大量集水等。原因分析:自然循环中,水在系统中的流动是靠供、回水的密度差产生的作用压头,数值较小,如果系统阻力较大会造成热水循环差,导致部分房间不热。室内管道安装不合理,坡度不够,有的还会出现反坡现象,使系统排气不畅,导致散热器集气。膨胀水箱容积小,导致水箱溢水。对策:放大供、回水管径,尽量降低系统阻力;管道按设计坡度进行安装,杜绝反坡;提高膨胀水箱位置。
三是房间供热正常,但达不到设计温度。原因分析:(一)热负荷计算有误,只计算基本耗热量,未考虑门窗渗入冷空气等的耗热量;(二)维护结构保温差,达不到设计的传热系数;(三)供、回水温度达不到设计值。对策:增加散热器数量。热负荷计算时应考虑全面;选择品质优良的保温层对维护结构保温;提高供、回水温度。
2、水平失调和垂直失调
一是末端建筑物暖气不热。原因分析:末端建筑物暖气不热的主要原因,一般是热网的水平失调。设计时水力平衡考虑不周,造成离锅炉房近端建筑物的流量过多,而流入距锅炉房远端建筑物的流量过少。对策:防止热网水平失调的主要措施是在设计时合理布置管网,认真进行水力计算,在余压过大的建筑物入口处安装平衡阀,把热网末端的管径适当放大。
二是上行下给式采暖系统存在上层过热,下层室温低的现象。原因分析:出现上层热下层不热的情况在单管系统中,原因很多,通常是在冷风渗透耗热量的计算时,未考虑建筑物的热压作用,下层算的热负荷比实际少,上层则相反。同时,在计算散热器数量时,未考虑管道散入房间的热量,将房间的热负荷全部作为散热器的负荷。这样上层(即顺水流方向起始处)的散热器和管道合在一起的散热量大于房间热负荷。上层的散热器越多,水温降越大,使进入下层散热器的水温就越低,因为未考虑管道降温,下层散热器的表面温度低于计算值,造成下层室温较低。而上行下给双管系统则主要是因为设计时考虑不周,导致双管系统上层下层重力水头的差别很大,出现垂直失调。对策:为解决上行下给单管系统上热下冷现象,在计算散热器时,应扣除管道的散热量后再计算出散热器片数。同时应计算热媒的管道温降,做适当的附加。对于上行下给双管系统,主要在设计时应做水力平衡计算,特别要考虑重力水头的影响。
二、通风设计常见问题及处理措施分析
1、管道设计
一是通风系统风量达不到设计风量。原因分析:在工程设计中,由于建筑空间窄小,风管的变径或与设备的连接处空间不够,导致安装不合理,风管连接突然扩大、突然缩小、弯头制作不符合规范等,造成系统阻力增大,使风量减少。对策:风管变径时,断面积顺气流方向分为扩大与缩小两种情况,一般扩大斜度≤150,而缩小斜度≤300。为了保持上述斜度,变径管的长度L可按下法求得:
单边变径时,当h1=h2,L=│W1-W2│×7;
当W1=W2,L=│h1-h2│×7。
双边均变径时,
当│W1-W2│≥│h1-h2│时,L=│W1-W2│×3.5;
当│W1-W2│≤│h1-h2│时,L=│h1-h2│×3.5
弯头无导流叶片时,其弯曲半径R最小不得小于1/2W,(W———为风管的宽度),一般以1W为宜。导流叶片的弯头,由于受空间及障碍物的限制,弯头内侧的曲率半径小于1/2W,气流所形成的涡流大,压力损失多,为了降低阻力,此时需加导流叶片。当弯头之后,紧接有送风口时,宜采用带导流叶片的直角弯头或用方形小室,这样可兼作消声,且不必加导流叶片设计风管系统时,弯头与弯头之间,弯头与出风口之间的距离不能太小。太小则涡流严重,气流分布不均,出风口达不到设计风量。
①普通弯头不带导流叶片时,L≥8W;
②普通彎头带导流叶片时,L=4W~8W;
③直角弯头带导流叶片时,L≤4W。若出风口装在两个相近且为45°的弯头下侧时,不论弯头有无导流叶片,必须L1>L2,且L2≥8W。
二是通风系统运行时风管产生的噪音大。原因分析:管内风速过大,使风管产生的噪音大。对策:在干管处安装消声器,在通风设计时风速应在允许的范围内。建议的风速既考虑
到系统的运行费用,也考虑到不要因风速太大而对周围环境产生干扰。
2、气流组织与风口布置
一是室内采用风机盘管空调供暖时,室内温度梯度大,热风下不来。原因分析:送风口和回风口安装距离近,造成送风不经过室内直接吸入回风口,回风短路,下部空气循环效果差。对策:将回风口的位置适当的向下调整,使室内空气循环通畅。
二是室内采用风机盘管空调制冷时,送风口采用的单层百叶,靠门的一侧很冷,而房间内的温度却比较高。原因分析:风口选择不合适,使气流扩散不到边角处,导致室内温度不均匀。对策:将单层百叶送风口改为双层百叶送风口,双层百叶送风口可以在施工验收时一次调节好,以后也不用常调,能解决整个房间的气流均匀问题。
3、风机的应用
一是在风机新安装后,进行正式运转时发生流量时大时小的现象。原因分析:产生这种现象的原因,主要有以下两点:a.管网阻力实际值与计算值相差过大。由一般管网特性方程式H=KQ2(K为阻力系数)可知,如实际值K小于计算值K时,则流量增大;若实际值K大于计算值K,则流量减小。b.选择时未考虑风机本身全压值偏差的影响,风机标签标定的性能是标准状况下的性能,各地区使用条件变了,就会出现偏差,当风机实际全压为正偏差时,则流量增大;为负偏差时,则流量减小。对策:重新核算或更换风机或修改管网。
二是当风机运行一段时间后出现流量不足的情况。原因分析:风机转速降低;管网阻力增大;可能管网有漏风、堵塞等情况;风机长时间运转后,轴承磨损严重。对策:风机需调整到额定转速;或调整管网阻力;或更换风机部件。
参考文献
[1]何天祺.供暖通风与空气调节[M].重庆:重庆大学出版社,2002.
[2]李娥飞.暖通空调设计与通病分析[M].北京:中国建筑工业出版社,2004.
关键词: 采暖; 通风; 问题; 对策;
Abstract: Along with the rapid development of China's economy, construction industry as the center of the economic development by municipal government at all levels to subsequent construction design quality were also concerned examination department at all levels. This paper mainly through existing in the design of heating of gas, water level set disorder and vertical disorders and problems were analyzed, and the design of ventilation air distribution and draught layout, duct design and fan selection some problems in the analysis, summarizes some design methods to solve the problems. Available for reference to fellow.
Key Words: Heating; Ventilation; Problem; Countermeasures
中图分类号:S611 文献标识码:A 文章编号
前言
采暖、通风系统中出现的问题会影响系统的正常运行,通过对采暖设计中存在的集气、热网水平失调和垂直失调等问题进行分析,及对通风设计中气流组织与风口布置、风管设计和风机选型中存在的一些问题进行分析,总结了一些解决问题的方法,供在今后设计中参考。
一、采暖设计常见问题
采暖系统分为机械循环热水采暖系统和自然循环热水采暖系统。机械循环热水采暖系统是以水泵为循环动力,不受锅炉房位置高低及系统作用半径的限制,管中流速较大。系统所带的环路、支立管数较多,成为一个闭式的循环热水网,是一个复杂的水力系统。自然循环热水采暖系统是靠供、回水的密度差产生的作用压头克服系统阻力的,一般压头较小,管中流速一般较小。常采用异程式设计,易于平衡和调节。
1、集气、反坡和热负荷计算
一是供暖期间,个别房间散热器不热,其它房间散热器良好。房间立管、支管符合安装要求。原因分析:散热器内部集气。在热水系统中,空气是最有害的因素。在系统充水前存在的空气、通过不严密处渗入的空气、从水中分解出来的空气是热水供暖系统空气的主要来源。当管道中有空气积存时,往往会影响热水的正常循环。空气比水轻,空气都积存于系统的最高点,因此在采暖系统的设计中,一定要在系统的高处安装放气阀。对策:打开散热器的放气阀,直到有少量的水流出再关闭阀门。
二是用土暖气供暖,系统安装完后出现多种情况,如部分房间不热,打开散热器旁的放气阀,放出很多热蒸气,水箱在系统运行时不断的向外溢水,使地面大量集水等。原因分析:自然循环中,水在系统中的流动是靠供、回水的密度差产生的作用压头,数值较小,如果系统阻力较大会造成热水循环差,导致部分房间不热。室内管道安装不合理,坡度不够,有的还会出现反坡现象,使系统排气不畅,导致散热器集气。膨胀水箱容积小,导致水箱溢水。对策:放大供、回水管径,尽量降低系统阻力;管道按设计坡度进行安装,杜绝反坡;提高膨胀水箱位置。
三是房间供热正常,但达不到设计温度。原因分析:(一)热负荷计算有误,只计算基本耗热量,未考虑门窗渗入冷空气等的耗热量;(二)维护结构保温差,达不到设计的传热系数;(三)供、回水温度达不到设计值。对策:增加散热器数量。热负荷计算时应考虑全面;选择品质优良的保温层对维护结构保温;提高供、回水温度。
2、水平失调和垂直失调
一是末端建筑物暖气不热。原因分析:末端建筑物暖气不热的主要原因,一般是热网的水平失调。设计时水力平衡考虑不周,造成离锅炉房近端建筑物的流量过多,而流入距锅炉房远端建筑物的流量过少。对策:防止热网水平失调的主要措施是在设计时合理布置管网,认真进行水力计算,在余压过大的建筑物入口处安装平衡阀,把热网末端的管径适当放大。
二是上行下给式采暖系统存在上层过热,下层室温低的现象。原因分析:出现上层热下层不热的情况在单管系统中,原因很多,通常是在冷风渗透耗热量的计算时,未考虑建筑物的热压作用,下层算的热负荷比实际少,上层则相反。同时,在计算散热器数量时,未考虑管道散入房间的热量,将房间的热负荷全部作为散热器的负荷。这样上层(即顺水流方向起始处)的散热器和管道合在一起的散热量大于房间热负荷。上层的散热器越多,水温降越大,使进入下层散热器的水温就越低,因为未考虑管道降温,下层散热器的表面温度低于计算值,造成下层室温较低。而上行下给双管系统则主要是因为设计时考虑不周,导致双管系统上层下层重力水头的差别很大,出现垂直失调。对策:为解决上行下给单管系统上热下冷现象,在计算散热器时,应扣除管道的散热量后再计算出散热器片数。同时应计算热媒的管道温降,做适当的附加。对于上行下给双管系统,主要在设计时应做水力平衡计算,特别要考虑重力水头的影响。
二、通风设计常见问题及处理措施分析
1、管道设计
一是通风系统风量达不到设计风量。原因分析:在工程设计中,由于建筑空间窄小,风管的变径或与设备的连接处空间不够,导致安装不合理,风管连接突然扩大、突然缩小、弯头制作不符合规范等,造成系统阻力增大,使风量减少。对策:风管变径时,断面积顺气流方向分为扩大与缩小两种情况,一般扩大斜度≤150,而缩小斜度≤300。为了保持上述斜度,变径管的长度L可按下法求得:
单边变径时,当h1=h2,L=│W1-W2│×7;
当W1=W2,L=│h1-h2│×7。
双边均变径时,
当│W1-W2│≥│h1-h2│时,L=│W1-W2│×3.5;
当│W1-W2│≤│h1-h2│时,L=│h1-h2│×3.5
弯头无导流叶片时,其弯曲半径R最小不得小于1/2W,(W———为风管的宽度),一般以1W为宜。导流叶片的弯头,由于受空间及障碍物的限制,弯头内侧的曲率半径小于1/2W,气流所形成的涡流大,压力损失多,为了降低阻力,此时需加导流叶片。当弯头之后,紧接有送风口时,宜采用带导流叶片的直角弯头或用方形小室,这样可兼作消声,且不必加导流叶片设计风管系统时,弯头与弯头之间,弯头与出风口之间的距离不能太小。太小则涡流严重,气流分布不均,出风口达不到设计风量。
①普通弯头不带导流叶片时,L≥8W;
②普通彎头带导流叶片时,L=4W~8W;
③直角弯头带导流叶片时,L≤4W。若出风口装在两个相近且为45°的弯头下侧时,不论弯头有无导流叶片,必须L1>L2,且L2≥8W。
二是通风系统运行时风管产生的噪音大。原因分析:管内风速过大,使风管产生的噪音大。对策:在干管处安装消声器,在通风设计时风速应在允许的范围内。建议的风速既考虑
到系统的运行费用,也考虑到不要因风速太大而对周围环境产生干扰。
2、气流组织与风口布置
一是室内采用风机盘管空调供暖时,室内温度梯度大,热风下不来。原因分析:送风口和回风口安装距离近,造成送风不经过室内直接吸入回风口,回风短路,下部空气循环效果差。对策:将回风口的位置适当的向下调整,使室内空气循环通畅。
二是室内采用风机盘管空调制冷时,送风口采用的单层百叶,靠门的一侧很冷,而房间内的温度却比较高。原因分析:风口选择不合适,使气流扩散不到边角处,导致室内温度不均匀。对策:将单层百叶送风口改为双层百叶送风口,双层百叶送风口可以在施工验收时一次调节好,以后也不用常调,能解决整个房间的气流均匀问题。
3、风机的应用
一是在风机新安装后,进行正式运转时发生流量时大时小的现象。原因分析:产生这种现象的原因,主要有以下两点:a.管网阻力实际值与计算值相差过大。由一般管网特性方程式H=KQ2(K为阻力系数)可知,如实际值K小于计算值K时,则流量增大;若实际值K大于计算值K,则流量减小。b.选择时未考虑风机本身全压值偏差的影响,风机标签标定的性能是标准状况下的性能,各地区使用条件变了,就会出现偏差,当风机实际全压为正偏差时,则流量增大;为负偏差时,则流量减小。对策:重新核算或更换风机或修改管网。
二是当风机运行一段时间后出现流量不足的情况。原因分析:风机转速降低;管网阻力增大;可能管网有漏风、堵塞等情况;风机长时间运转后,轴承磨损严重。对策:风机需调整到额定转速;或调整管网阻力;或更换风机部件。