摘要:在电力系统中,对电气设备实施必要的保护十分重要,微机保护方法是当前最为广泛的保护方法,对继电保护二次回路的隐患进行排查,积极采取隐患预防措施,可以减少电气设备及微机保护装置的安全隐患。本文针对继电保护二次回路的隐患排查以及相应的预防措施进行分析,通过相应的实践,找到解决二次回路隐患的方法。
关键词:继电保护隐患排查防范措施
Abstract: in the electric power system, the need to protect the electrical equipment is very important, and the protection of the microcomputer protection method is currently the most widely method, the hidden trouble of the secondary circuit of relay protection testing, hazard prevention measures actively, can reduce electrical equipment and microcomputer protection device safe hidden trouble. Aiming at the hidden perils of relay protection secondary circuit and the corresponding prevention measures were analyzed, and through the corresponding practice, find a way to solve the secondary loop hidden trouble.
Keywords: relay protection Hidden perilspreventive measures
中图分类号:TM77 献标识码:A 文章编号:2095-2104(2012)01-0020-02
微机保护装置的广泛应用大大提高了电气设备的可靠性,相应的保护装置开始向着微机化管理的时代发展。在继电保护中,二次回路的故障解决还有待进一步发展。本文主要阐述了继电保护二次回路的隐患排查以及相应的预防措施,旨在给相关工作人员参考,共同提高检修技术水平。
1 二次回路故障造成的不良影响
首先,对二次回路断线给继电保护造成的影响进行分析。当二次回路断线后,继电保护中无法得到正确的电压信号,而所获得的信号存在较大的误差,最终导致保护工作无法正常运行。图1给出了A相一次断线,二次断线对比图。针对这一问题,很多系统中采用的是电压互感器断线检测,当发生断线现象时,自动闭锁发生动作,大大降低了误判的概率。对于互感器二次三相断线来说,此时的保护为三相无压保护,在微机保护中,可以通过三相无压但是存在电流的依据进行判断[1]。对于三相以及两相断线来说,不同的保护装置有不同的判断依据。
图1 A相一次断线,二次断线对比图
其次,对二次回路多点接地造成的影响进行分析[2]。此时,中性点的线电压会发生偏移,相电压会出现升高或是降低的现象,从而发生相应的变化。如果相电压升高,线路发生正向故障,电压的偏移导致方向元件在判别时难度较低,由此保证了继电器依然能够稳定可靠的运行。但是,一旦出现反向故障,相应的整定值和电压的偏移值将会发生变化,将有可能导致接地距离继电器出现误判,最终导致误动作[3]。如果相电压降低,在线路发生正向故障的情况下,接地点之间会发生抗阻现象,通常情况下,这一现象不会造成太大的偏移电压,与之相应的继电器依然可以正常工作。但是,一旦出现有方向故障,就算接地距离继电器没有发生误判断和误动作,零序功率方向继电器也很有可能会出现误判断。
2 二次回路隐患的排查
当二次回路出现了安全隐患后,如果没有及时进行隐患排查,将会酿就很大的安全事故。只有有针对性的进行了隐患排查,才有可能找到科学合理的方法对事故进行处理。具体来讲,首先是对发变组保护变组故障录波器的相应记录进行调取,如果这些记录都没有保存,则需要调取机组的差流、相角值等采样数据。如果比较了现场测量值后未发现异常现象,则应该对网控故障录波器中的启动记录进行调取。同时,在调取过程中,如果没有找到当天的启动记录,则可以判断出出现的故障不是因为区外故障引起的。发变组保护装置属于一种成套保护装置,它能够通过相应的录波功能实现相应量的实时记录,如:模拟采样值、差流值等等。通过对发变组录波图的分析可以看出,一旦发电机的U相电流中出现了畸变现象,同时相应的中性点电流波形表现为正常,在发电机的U相中出现了二次差流,则可以看出,该故障不属于一次设备的故障,并且可以断定故障很大可能是因为发变组的保护装置以及二次回路中存在问题。在后续检查过程中,需要对机组进行停机消缺,当经过检查后发现发变组保护装置中采样波形正常,则可知录波装置得到的波形也是正常的。在完成以上判断之后,需要对全部的接线端子进行排查,在排查过程中,要检查电流互感器的二次接线端子盒,如果接线上的螺丝颜色发生改变,需要进行接线拆除工作,同时还应该将绝缘胶布打开进行检查,看其根部是否发生了断裂。
3 继电保护二次回路隐患的预防措施
通过分析可知继电保护二次回路中出现隐患将会造成重大的设备失控现象,导致大面积停电,损坏重要设备。进行必要的隐患预防显得十分关键,本节对此展开论述。
3.1 多CPU容错技术
随着科学技术的不断发展,开发CPU容错技术也成为一大热点。在现代继电保护中,CPU容错技术也逐渐得到了应用,它能够有效降低保护系统硬件问题导致误判的概率,大大的提高了继电保护装置的可靠性。同時,应用CPU 容错技术还可以有效提高系统的工作效率和正确性,如:成组数据的处理效率、信息共享的正确性等。此外,多CPU的应用还可以实现在单一CPU故障的情况下依然保证工作的正常,因为此时其他的CPU可以担当起工作任务,大大提高了继电保护二次回路工作的稳定性[4]。
3.2 强化相应二次回路接线的完整性
近年来,常常会出现由于PT和CT的质量问题而导致二次回路中存在隐患的现象,一旦这些隐患演变成故障,将会使得设备停止运行,相应的保护也会退出。因此,有必要重视PT回路的断线现象,同时也应该对CT的质量进行严格把关。在具体的工作实际中,首先应该从回路的薄弱环节开始,进行回路断线的查找,使用的查找方法可以依照二次回路施工图进行;并且以此为依据进行PT一次熔断器和二次刀闸的检查,逐步排查隐患。在进行CT的选择时,相关工作人员要做好充分的调研工作,在CT投入使用之前,要对其进行全面的检查。同时,对CT回路的定期检验工作也应该受到重视,工作人员应该提高工作质量,在全面检查过程中要参考相应的历史数据。
3.3直流回路缺陷的预防
在直流回路缺陷的预防上,首先应该重视直流回路的全面检查,通过相应的保护检验对系统二次回路元件进行定期更换。其次,要为设备提供良好的运行环境,如:在振动场所安装设备的时候应该采取必要的防震措施。最后,还应该做好设备的改造工作。
4 结论
总之,微机继电保护装置的广泛使用提高了电力系统的可靠性,此时,人员应该高度关注继电保护二次回路的隐患问题,及时发现并排除其中的隐患,防止其演化为故障。本文针对继电保护二次回路的隐患排查以及相应的预防措施进行分析,通过相应的实践,找到解决二次回路隐患的方法。
参考文献:
[1]杨凯,莫欣.继电保护二次回路检修维护问题探讨[J].中国科技财富,2011(22):15-17
[2]程文英,董红,高金锴.继电保护二次回路隐患排查及防范[J].吉林电,2011(39):33-35
[3]谭永湛.继电保护二次回路检修维护中的若干问题分析[J].企业技术开发(学术版),2011(07):11-12
[4]张美枝,张靖. 电厂继电保护的二次回路改造问题[J].科技传播. 2013(04):28-29
关键词:继电保护隐患排查防范措施
Abstract: in the electric power system, the need to protect the electrical equipment is very important, and the protection of the microcomputer protection method is currently the most widely method, the hidden trouble of the secondary circuit of relay protection testing, hazard prevention measures actively, can reduce electrical equipment and microcomputer protection device safe hidden trouble. Aiming at the hidden perils of relay protection secondary circuit and the corresponding prevention measures were analyzed, and through the corresponding practice, find a way to solve the secondary loop hidden trouble.
Keywords: relay protection Hidden perilspreventive measures
中图分类号:TM77 献标识码:A 文章编号:2095-2104(2012)01-0020-02
微机保护装置的广泛应用大大提高了电气设备的可靠性,相应的保护装置开始向着微机化管理的时代发展。在继电保护中,二次回路的故障解决还有待进一步发展。本文主要阐述了继电保护二次回路的隐患排查以及相应的预防措施,旨在给相关工作人员参考,共同提高检修技术水平。
1 二次回路故障造成的不良影响
首先,对二次回路断线给继电保护造成的影响进行分析。当二次回路断线后,继电保护中无法得到正确的电压信号,而所获得的信号存在较大的误差,最终导致保护工作无法正常运行。图1给出了A相一次断线,二次断线对比图。针对这一问题,很多系统中采用的是电压互感器断线检测,当发生断线现象时,自动闭锁发生动作,大大降低了误判的概率。对于互感器二次三相断线来说,此时的保护为三相无压保护,在微机保护中,可以通过三相无压但是存在电流的依据进行判断[1]。对于三相以及两相断线来说,不同的保护装置有不同的判断依据。
图1 A相一次断线,二次断线对比图
其次,对二次回路多点接地造成的影响进行分析[2]。此时,中性点的线电压会发生偏移,相电压会出现升高或是降低的现象,从而发生相应的变化。如果相电压升高,线路发生正向故障,电压的偏移导致方向元件在判别时难度较低,由此保证了继电器依然能够稳定可靠的运行。但是,一旦出现反向故障,相应的整定值和电压的偏移值将会发生变化,将有可能导致接地距离继电器出现误判,最终导致误动作[3]。如果相电压降低,在线路发生正向故障的情况下,接地点之间会发生抗阻现象,通常情况下,这一现象不会造成太大的偏移电压,与之相应的继电器依然可以正常工作。但是,一旦出现有方向故障,就算接地距离继电器没有发生误判断和误动作,零序功率方向继电器也很有可能会出现误判断。
2 二次回路隐患的排查
当二次回路出现了安全隐患后,如果没有及时进行隐患排查,将会酿就很大的安全事故。只有有针对性的进行了隐患排查,才有可能找到科学合理的方法对事故进行处理。具体来讲,首先是对发变组保护变组故障录波器的相应记录进行调取,如果这些记录都没有保存,则需要调取机组的差流、相角值等采样数据。如果比较了现场测量值后未发现异常现象,则应该对网控故障录波器中的启动记录进行调取。同时,在调取过程中,如果没有找到当天的启动记录,则可以判断出出现的故障不是因为区外故障引起的。发变组保护装置属于一种成套保护装置,它能够通过相应的录波功能实现相应量的实时记录,如:模拟采样值、差流值等等。通过对发变组录波图的分析可以看出,一旦发电机的U相电流中出现了畸变现象,同时相应的中性点电流波形表现为正常,在发电机的U相中出现了二次差流,则可以看出,该故障不属于一次设备的故障,并且可以断定故障很大可能是因为发变组的保护装置以及二次回路中存在问题。在后续检查过程中,需要对机组进行停机消缺,当经过检查后发现发变组保护装置中采样波形正常,则可知录波装置得到的波形也是正常的。在完成以上判断之后,需要对全部的接线端子进行排查,在排查过程中,要检查电流互感器的二次接线端子盒,如果接线上的螺丝颜色发生改变,需要进行接线拆除工作,同时还应该将绝缘胶布打开进行检查,看其根部是否发生了断裂。
3 继电保护二次回路隐患的预防措施
通过分析可知继电保护二次回路中出现隐患将会造成重大的设备失控现象,导致大面积停电,损坏重要设备。进行必要的隐患预防显得十分关键,本节对此展开论述。
3.1 多CPU容错技术
随着科学技术的不断发展,开发CPU容错技术也成为一大热点。在现代继电保护中,CPU容错技术也逐渐得到了应用,它能够有效降低保护系统硬件问题导致误判的概率,大大的提高了继电保护装置的可靠性。同時,应用CPU 容错技术还可以有效提高系统的工作效率和正确性,如:成组数据的处理效率、信息共享的正确性等。此外,多CPU的应用还可以实现在单一CPU故障的情况下依然保证工作的正常,因为此时其他的CPU可以担当起工作任务,大大提高了继电保护二次回路工作的稳定性[4]。
3.2 强化相应二次回路接线的完整性
近年来,常常会出现由于PT和CT的质量问题而导致二次回路中存在隐患的现象,一旦这些隐患演变成故障,将会使得设备停止运行,相应的保护也会退出。因此,有必要重视PT回路的断线现象,同时也应该对CT的质量进行严格把关。在具体的工作实际中,首先应该从回路的薄弱环节开始,进行回路断线的查找,使用的查找方法可以依照二次回路施工图进行;并且以此为依据进行PT一次熔断器和二次刀闸的检查,逐步排查隐患。在进行CT的选择时,相关工作人员要做好充分的调研工作,在CT投入使用之前,要对其进行全面的检查。同时,对CT回路的定期检验工作也应该受到重视,工作人员应该提高工作质量,在全面检查过程中要参考相应的历史数据。
3.3直流回路缺陷的预防
在直流回路缺陷的预防上,首先应该重视直流回路的全面检查,通过相应的保护检验对系统二次回路元件进行定期更换。其次,要为设备提供良好的运行环境,如:在振动场所安装设备的时候应该采取必要的防震措施。最后,还应该做好设备的改造工作。
4 结论
总之,微机继电保护装置的广泛使用提高了电力系统的可靠性,此时,人员应该高度关注继电保护二次回路的隐患问题,及时发现并排除其中的隐患,防止其演化为故障。本文针对继电保护二次回路的隐患排查以及相应的预防措施进行分析,通过相应的实践,找到解决二次回路隐患的方法。