For utilization of the residual heat of flue gas to drive the absorption chillers,a lithium-bromide falling film in vertical tube type generator is presented.A mathematical model was developed to simulate the heat and mass coupled problem of laminar falling film evaporation in vertical tube.In the model,the factor of mass transfer was taken into account in heat transfer performance calculation.The temperature and concentration fields were calculated.Some tests were conducted for the factors such as Re number,heating flux,the inlet concentration and operating pressure which can affect the heat and mass transfer performance in laminar falling film evaporation.The heat transfer performance is enhanced with the increasing of heat flux.An increasing inlet concentration can weaken the heat transfer performance.The operating pressure hardly affects on heat and mass transfer.The bigger inlet Re number means weaker heat transfer effects and stronger mass transfer.The mass transfer obviously restrains the heat transfer in the falling film solution.The relation between dimensionless heat transfer coefficient and the inlet Re number is obtained.
For utilization of the residual heat of flue gas to drive the absorption chillers, a lithium-bromide falling film in vertical tube type generator is presented. A mathematical model was developed to simulate the heat and mass coupled problem of laminar falling film evaporation in vertical tube .In the model, the factor of mass transfer was taken into account in heat transfer performance calculation. Temperature and concentration fields were calculated.Some tests were conducted for the factors such as re number, heating flux, the inlet concentration and operating pressure which can affect the heat and mass transfer performance in laminar falling film evaporation. The increasing transfer concentration is weak with the heat transfer performance. The operating pressure hardly affects on heat and mass transfer. bigger inlet Re number means weaker heat transfer effects and stronger mass transfer.The mass transfer obviously trains the heat transfer in the falling film solution. The relation between dimensionless heat transfer coefficient and the inlet Re number is obtained.