论文部分内容阅读
通过对深圳某工业厂房分别选用常规冷凝除湿空调系统和溶液除湿空调系统进行系统设计和理论计算分析,比较了两类空调系统的能耗及COP。在夏季室外设计工况下,常规冷凝除湿空调系统的COP为2.94,溶液除湿空调系统的COP为5.42。室外空气含湿量越小,对提高溶液除湿系统的性能越有利。溶液除湿空调系统在节能方面具有较大的优势。
Through the systematic design and theoretical calculation and analysis of the conventional condensing dehumidification air-conditioning system and the solution dehumidification air-conditioning system for an industrial plant in Shenzhen, the energy consumption and COP of the two types of air-conditioning systems are compared. Under summer outdoor design conditions, the COP of the conventional condensing dehumidification air conditioning system was 2.94 and the COP of the solution dehumidification air conditioning system was 5.42. The smaller the outdoor air moisture content, the better the performance of the solution dehumidification system. Solution dehumidification air conditioning system has greater advantages in energy conservation.