摘要:近年来,随着建筑市场的开放,建筑与安装业迅猛发展对建筑的功能要求不断提高,特别是智能大楼的出现,使得电气安装工程成为房屋建筑工程中重要组成部分。在建设工程中,电气安装质量的好坏轻则影响整体工程的质量,重则会危及用户的安全。因此,本文重点研究了建筑电气工程施工质量问题,就防治电气施工质量通病提出一些防治措施。
关键字:房屋建筑;机电安装;质量通病
Abstract: in recent years, with the opening of the construction market, construction and installation industry rapid development of building functional requirements continuously improve, especially the emergence of intelligent building, make electrical installation to be in housing construction project is an important part. In the construction engineering, electrical installation quality of light will influence the overall project quality, heavy will endanger the safety of users. Therefore, this article focuses on the construction of electrical engineering construction quality problem, the prevention and control of electrical construction quality problems puts forward some prevention and control measures.
Key words: housing construction; Mechanical and electrical installation; Quality common fault
中圖分类号:X503.5文献标识码:A 文章编号:2095-2104(2012)
前言
房屋建筑机电安装工程包含了中央空调、防排烟、生活给排水、消火栓、喷洒、楼宇自控、保安监控、消防自动报警、综合布线、有线电视、公共广播、动力、照明等系统。工期短,结构复杂,施工难度大,施工质量要求高是房屋建筑机电安装的特点。受这一特点和其他因素的影响,建筑机电安装工程存在一些质量通病,施工者需要引起注意。
一、管路敷设
1、现象:
钢管和PVC管壁厚不足,钢管毛刺,钢管防腐,线管堵塞,预埋线管处的裂缝,线管保护层不够,金属管未做跨接接地线或者不论材质一律焊跨接接地线以及镀锌管直接采用套管熔焊连接、套管连接不牢;
2、防治措施:
⑴ 在配管工程施工时,一定要加强进场原材料的质量控制,钢管厚度应在2mm以上,PVC管也得满足规范要求,不应小于1.6mm。
⑵ 进场的焊接钢管不宜毛刺过多,否则立即离场。在使用切割机切割线管时,毛刺很多,一定要清理。在布管时一定要将管口毛刺再清一遍。
⑶ 焊接钢管与混凝土接触面不用做防腐,而管内则需要反复刷防腐漆。
⑷ 在浇筑完混凝土后,及时吹管,检查管子堵塞情况。如有问题,及时整改(改变路径)
⑸ 预埋线管,特别是多根线管的集散处使截面砼受到削弱,从而引起应力集中,容易导致裂缝发生的薄弱部位。当预埋线管的直径较大,开间宽度也较大,并且线管的敷设走向又垂直于砼的收缩和受拉力向时,就很容易发生楼面裂缝。为此,强弱电线管布局合理,尽量不要叠加,在线管薄弱处,做加固措施。
⑹ 线管一定要放置在板的上下筋之间以及墙体筋内,按照图纸以确保线管有三公分的保护层。按照规范管路保护层厚度应大于15mm。
⑺ 镀锌管壁厚小于2mm的钢导管不得套管熔焊连接,套管与紧固螺钉应配套并经过强度和电气连续性试验;
⑻ 非镀锌钢导管采用螺纹连接时,连接处的两端焊跨接接地线;镀锌钢导管采用螺纹连接时,连接处两端用专用接地卡固定跨接接地线。
二、配电箱箱体预埋
现象:
箱体电焊开孔、开长孔,管直入箱体,箱体壁厚、锈蚀、暗配电箱外壳变形,箱体内设置不全
防治措施:
在混凝土墙或砖墙上固定明装配电箱时,先将分线盒内杂物清理干净,然后将导线理顺,分清支路和相序,按支路绑扎成束。待箱体找准位置后,将导线端头引至箱内,逐个压接在器具上,同时将保护地线压在明显的地方,并将箱调整平直后进行固定。在电具、仪表接线安装完毕后,先用仪表校对有无差错,调整无误后送电,并将卡片框内的卡片填写好部位、编上号,箱门贴系统图。
结构配合时期根据结构和装修做法确定配电箱暗装做法。
(1)结构配合时期将配电箱箱体预埋在结构中,箱体比较大时内部必须增加固定支撑以防止变形,标高符合设计要求,接地正确,拆模后及时清理并做好箱体保护工作,门窗封闭之后开始箱芯安装,做好成品保护,箱芯安装时配线美观,回路标注清楚,墙面做法完成后安装箱门,箱门紧贴墙面、开启灵活,贴有系统图。
(2)进箱一管一孔,当箱体上敲落孔不够时,用开孔器开孔;连接完毕做跨接地线,不能用箱体做为接地线的导体;箱体、管路连接固定好后,箱内清理干净,用盖板封闭,避免土建湿作业污染。
(3)PE线安装应牢固明显,导线选择如下:
相导线的截面积S(平方毫米) 相应的保护导线的最小面积Sp
S ≤ 16 Sp = S
16 < S ≤ 35 Sp =16
400≥S > 35 Sp = S/2
三、接地防雷
1、现象
接地装置的材料品种选择不当;钢材不是热浸镀锌产品;材料的规格,尺寸(厚度或直径)小;接地体(极)间距大,连接工艺不符合要求;接地装置未按设计要求(点数和位置)设置测试点;防雷接地的人工接地装置在经人行通道处的埋设深度不够;接地线(PE)的截面积偏小。
2、防治措施
(1)选用接地材料的品种、材质、规格、尺寸要符合设计要求和相应材料的国家标准。如设计上选用的钢材为热浸镀锌扁钢(圆钢),就不要用角钢或钢管来代替,更不允许选用冷镀锌的产品。
在选用、订货和材料进场验收时,可用下面方法,简单地辨别接地装置的钢材是否为热浸镀锌钢材:镀锌钢材有热镀锌和冷镀锌两种,经过热浸镀锌的金属材料,其镀锌层较冷镀锌沾接金属表面的强度大,耐腐蚀性能强,但镀锌层表面有锌瘤及锌结晶花纹,表面较显粗糙。镀锌金属表面镀锌层光泽眩目,金属表面光滑,抗腐蚀性交差。
材料的规格、尺寸(厚度或直径)要符合设计要求和规范规定。根据接地装置敷设的场合(地点),设计上所选用的材料,规格、尺寸必须满足规范规定。
防雷接地装置的人工接地装置的接地干线埋设,应先沿接地体(极)的线路开挖接地体(极)沟,接地体(极)沟验收合格后,再打入接地体(极)和敷设连接接地体(极)的接地干线,做好工序交接记录、隐蔽工程验收记录,前一道工序未经验收合格,不得进行下一道工序。
接地体(极)的间距应按设计的要求施工,位置应正确,才能达到设计的快速疏散雷电的效果。
(2)人工接地装置或利用建筑物基础钢筋的接地装置,必须在地面以上按设计和规范要求的位置设测试点。
在主体施工时,若避雷引下线利用柱子钢筋,按设计要求的位置(如设计不明确,可在室外距地面500mm处),于建筑物的四个角焊出接地电阻测试端子。
(3)防雷接地的人工接地装置的接地干线埋设,在设计阶段或在施工时,一般尽量避免防雷接地干线穿越人行通道,以防止 雷击时跨步电压过高而危及人身安全。如果无法避开,需要穿越人形通道,接地干线的深度应符合规范要求,即经人行通道处埋地深度应大于等于1m,且应采取均压措施或在其上方普卵石或沥青地面;
(4)旋转接地干线的截面积时,要注意符合设计和规范要求。套管之间的所有空隙填塞密实。
四、吊顶内配管配线混乱不规则
1、现象
(1)配管走向不规则,线路歪斜,高低起伏,吊架之间间距过大,有的配管无单独吊支架,利用龙骨吊筋或直接放在龙骨上。
(2)导线外露在吊顶内,导线连接的接头在吊顶内,箱盒位置不当,甚至没有盖板,使盒内导线外露。
(3)金属钢管跨接接地线焊接质量差,有夹渣,焊穿及“点焊”现象。
(4)金属软管来作跨接接地线保护。金属软管长度太长。
2、控制措施
(1)吊平顶内有电气配管应按明配管线的要求施工,基本上做到“横平竖直”,不应斜走或交叉。吊支架的设置也应按明配管要求,间距均匀对称。电气管线的吊支架应单独设置,不得利用平顶龙骨的筋作支架,而不得将管线直接放在平顶龙骨上。
(2)吊平顶内导线,不论是强电还是弱电,都应穿入电线管内保护。财线的连接头应在接线盒内或在灯具内,严禁明露在吊顶内。灯具近旁应有一只接线盒,接线盒位置应装于便于检查维修并加盖板,接线盒本身应可靠接地。
(3)采用钢管的其跨接接地线焊接要求应符合规范规定,不得“点焊”。利用金属软管连接灯具的金属软管本身应作跨接接地保护,但不得作接地保护线。金属软管的长度不宜超过1米。采用PVC刚性塑料管的。金属软管宜采用外层涂以塑料保护层的软管。
五、照明器具安装
1、个别灯具的型号、规格、安装位置、安装高度不符合设计要求。如厨厕间设计为防水灯,而实际安装多为普通灯。应严格按设计要求进行施工。
高度低于2.4m的灯具,其金属外壳未做保护接地。GB50303-2002中19.1.6条要求:当灯具距地面高度小于2.4m(含2.4m)时,灯具的可接近裸露导体必须接地(PE)或接零(PEN)要可靠。并应有专用接地螺栓,具有标识。
3、当采用螺口灯头时,相线未接于螺口灯头中间的端子上,而将零线接在该端子上,极易造成人身安全事故。因此住宅装饰装修工程施工规范要求:连接开关、螺口灯具导线时,相线应先接开关,开关引出的相线应接在灯中心的端子上,零线应接在螺纹的端子上。
开关、插座安装问题: 1﹑开关不灵活或接触不良,插座插孔太松或太紧,影响了用户的正常使用。安全插座安全挡板损坏,起不到安全作用。进货时应认真检查,安装时或安装后发现不合格产品应及时更换,并应到有资质的部门进行检测。 2、住宅厨房、厕所内插座有的为普通插座。由于设计、施工的疏忽,给厨厕安装了普通插座,GB50327-2001中16.3.14条要求:厨房、卫生间应安装防溅插座。开关宜安装在门外开启侧的墙体上。在检查过程中也发现有的防溅插座未加橡胶垫,起不到其应有的作用,因此发现此问题应要求更换或补加橡胶垫。3、插座接线不符合规范要求,这一问题在工程中出现的较多。因此GB50303-2002中22.1.2条强制性条文要求:①单相两孔插座,面对插座的右孔或上孔与相线连接,左孔或下孔与零线连接;单相三孔插座,面对插座的右孔与相线连接,左孔与零线连接。②单相三孔、三相四孔及三相五孔插座的接地线接在上孔。插座的接地端子不与零线端子连接。同一场所的三相插座,接线的相序一致。③接地或接零线在插座间不串联连接。 结束语:它的存在是建筑工程质量的非常大的安全隐患,使广大居民在生活使用方面受到了極大的威胁。质量通病不容易消除,但它可以减小和控制。我们在整个施工过程中,要严格要求,按照规范标准进行操作,并加强管理,这样才可以消除或避免质量问题。
参考文献:
[1] 伍明峰.谈建筑电气施工管理的几点体会[J]建材与装饰,2007(10) .
[2] 李海林.提高工程质量[J].建筑管理现代化,2010(06).
关键字:房屋建筑;机电安装;质量通病
Abstract: in recent years, with the opening of the construction market, construction and installation industry rapid development of building functional requirements continuously improve, especially the emergence of intelligent building, make electrical installation to be in housing construction project is an important part. In the construction engineering, electrical installation quality of light will influence the overall project quality, heavy will endanger the safety of users. Therefore, this article focuses on the construction of electrical engineering construction quality problem, the prevention and control of electrical construction quality problems puts forward some prevention and control measures.
Key words: housing construction; Mechanical and electrical installation; Quality common fault
中圖分类号:X503.5文献标识码:A 文章编号:2095-2104(2012)
前言
房屋建筑机电安装工程包含了中央空调、防排烟、生活给排水、消火栓、喷洒、楼宇自控、保安监控、消防自动报警、综合布线、有线电视、公共广播、动力、照明等系统。工期短,结构复杂,施工难度大,施工质量要求高是房屋建筑机电安装的特点。受这一特点和其他因素的影响,建筑机电安装工程存在一些质量通病,施工者需要引起注意。
一、管路敷设
1、现象:
钢管和PVC管壁厚不足,钢管毛刺,钢管防腐,线管堵塞,预埋线管处的裂缝,线管保护层不够,金属管未做跨接接地线或者不论材质一律焊跨接接地线以及镀锌管直接采用套管熔焊连接、套管连接不牢;
2、防治措施:
⑴ 在配管工程施工时,一定要加强进场原材料的质量控制,钢管厚度应在2mm以上,PVC管也得满足规范要求,不应小于1.6mm。
⑵ 进场的焊接钢管不宜毛刺过多,否则立即离场。在使用切割机切割线管时,毛刺很多,一定要清理。在布管时一定要将管口毛刺再清一遍。
⑶ 焊接钢管与混凝土接触面不用做防腐,而管内则需要反复刷防腐漆。
⑷ 在浇筑完混凝土后,及时吹管,检查管子堵塞情况。如有问题,及时整改(改变路径)
⑸ 预埋线管,特别是多根线管的集散处使截面砼受到削弱,从而引起应力集中,容易导致裂缝发生的薄弱部位。当预埋线管的直径较大,开间宽度也较大,并且线管的敷设走向又垂直于砼的收缩和受拉力向时,就很容易发生楼面裂缝。为此,强弱电线管布局合理,尽量不要叠加,在线管薄弱处,做加固措施。
⑹ 线管一定要放置在板的上下筋之间以及墙体筋内,按照图纸以确保线管有三公分的保护层。按照规范管路保护层厚度应大于15mm。
⑺ 镀锌管壁厚小于2mm的钢导管不得套管熔焊连接,套管与紧固螺钉应配套并经过强度和电气连续性试验;
⑻ 非镀锌钢导管采用螺纹连接时,连接处的两端焊跨接接地线;镀锌钢导管采用螺纹连接时,连接处两端用专用接地卡固定跨接接地线。
二、配电箱箱体预埋
现象:
箱体电焊开孔、开长孔,管直入箱体,箱体壁厚、锈蚀、暗配电箱外壳变形,箱体内设置不全
防治措施:
在混凝土墙或砖墙上固定明装配电箱时,先将分线盒内杂物清理干净,然后将导线理顺,分清支路和相序,按支路绑扎成束。待箱体找准位置后,将导线端头引至箱内,逐个压接在器具上,同时将保护地线压在明显的地方,并将箱调整平直后进行固定。在电具、仪表接线安装完毕后,先用仪表校对有无差错,调整无误后送电,并将卡片框内的卡片填写好部位、编上号,箱门贴系统图。
结构配合时期根据结构和装修做法确定配电箱暗装做法。
(1)结构配合时期将配电箱箱体预埋在结构中,箱体比较大时内部必须增加固定支撑以防止变形,标高符合设计要求,接地正确,拆模后及时清理并做好箱体保护工作,门窗封闭之后开始箱芯安装,做好成品保护,箱芯安装时配线美观,回路标注清楚,墙面做法完成后安装箱门,箱门紧贴墙面、开启灵活,贴有系统图。
(2)进箱一管一孔,当箱体上敲落孔不够时,用开孔器开孔;连接完毕做跨接地线,不能用箱体做为接地线的导体;箱体、管路连接固定好后,箱内清理干净,用盖板封闭,避免土建湿作业污染。
(3)PE线安装应牢固明显,导线选择如下:
相导线的截面积S(平方毫米) 相应的保护导线的最小面积Sp
S ≤ 16 Sp = S
16 < S ≤ 35 Sp =16
400≥S > 35 Sp = S/2
三、接地防雷
1、现象
接地装置的材料品种选择不当;钢材不是热浸镀锌产品;材料的规格,尺寸(厚度或直径)小;接地体(极)间距大,连接工艺不符合要求;接地装置未按设计要求(点数和位置)设置测试点;防雷接地的人工接地装置在经人行通道处的埋设深度不够;接地线(PE)的截面积偏小。
2、防治措施
(1)选用接地材料的品种、材质、规格、尺寸要符合设计要求和相应材料的国家标准。如设计上选用的钢材为热浸镀锌扁钢(圆钢),就不要用角钢或钢管来代替,更不允许选用冷镀锌的产品。
在选用、订货和材料进场验收时,可用下面方法,简单地辨别接地装置的钢材是否为热浸镀锌钢材:镀锌钢材有热镀锌和冷镀锌两种,经过热浸镀锌的金属材料,其镀锌层较冷镀锌沾接金属表面的强度大,耐腐蚀性能强,但镀锌层表面有锌瘤及锌结晶花纹,表面较显粗糙。镀锌金属表面镀锌层光泽眩目,金属表面光滑,抗腐蚀性交差。
材料的规格、尺寸(厚度或直径)要符合设计要求和规范规定。根据接地装置敷设的场合(地点),设计上所选用的材料,规格、尺寸必须满足规范规定。
防雷接地装置的人工接地装置的接地干线埋设,应先沿接地体(极)的线路开挖接地体(极)沟,接地体(极)沟验收合格后,再打入接地体(极)和敷设连接接地体(极)的接地干线,做好工序交接记录、隐蔽工程验收记录,前一道工序未经验收合格,不得进行下一道工序。
接地体(极)的间距应按设计的要求施工,位置应正确,才能达到设计的快速疏散雷电的效果。
(2)人工接地装置或利用建筑物基础钢筋的接地装置,必须在地面以上按设计和规范要求的位置设测试点。
在主体施工时,若避雷引下线利用柱子钢筋,按设计要求的位置(如设计不明确,可在室外距地面500mm处),于建筑物的四个角焊出接地电阻测试端子。
(3)防雷接地的人工接地装置的接地干线埋设,在设计阶段或在施工时,一般尽量避免防雷接地干线穿越人行通道,以防止 雷击时跨步电压过高而危及人身安全。如果无法避开,需要穿越人形通道,接地干线的深度应符合规范要求,即经人行通道处埋地深度应大于等于1m,且应采取均压措施或在其上方普卵石或沥青地面;
(4)旋转接地干线的截面积时,要注意符合设计和规范要求。套管之间的所有空隙填塞密实。
四、吊顶内配管配线混乱不规则
1、现象
(1)配管走向不规则,线路歪斜,高低起伏,吊架之间间距过大,有的配管无单独吊支架,利用龙骨吊筋或直接放在龙骨上。
(2)导线外露在吊顶内,导线连接的接头在吊顶内,箱盒位置不当,甚至没有盖板,使盒内导线外露。
(3)金属钢管跨接接地线焊接质量差,有夹渣,焊穿及“点焊”现象。
(4)金属软管来作跨接接地线保护。金属软管长度太长。
2、控制措施
(1)吊平顶内有电气配管应按明配管线的要求施工,基本上做到“横平竖直”,不应斜走或交叉。吊支架的设置也应按明配管要求,间距均匀对称。电气管线的吊支架应单独设置,不得利用平顶龙骨的筋作支架,而不得将管线直接放在平顶龙骨上。
(2)吊平顶内导线,不论是强电还是弱电,都应穿入电线管内保护。财线的连接头应在接线盒内或在灯具内,严禁明露在吊顶内。灯具近旁应有一只接线盒,接线盒位置应装于便于检查维修并加盖板,接线盒本身应可靠接地。
(3)采用钢管的其跨接接地线焊接要求应符合规范规定,不得“点焊”。利用金属软管连接灯具的金属软管本身应作跨接接地保护,但不得作接地保护线。金属软管的长度不宜超过1米。采用PVC刚性塑料管的。金属软管宜采用外层涂以塑料保护层的软管。
五、照明器具安装
1、个别灯具的型号、规格、安装位置、安装高度不符合设计要求。如厨厕间设计为防水灯,而实际安装多为普通灯。应严格按设计要求进行施工。
高度低于2.4m的灯具,其金属外壳未做保护接地。GB50303-2002中19.1.6条要求:当灯具距地面高度小于2.4m(含2.4m)时,灯具的可接近裸露导体必须接地(PE)或接零(PEN)要可靠。并应有专用接地螺栓,具有标识。
3、当采用螺口灯头时,相线未接于螺口灯头中间的端子上,而将零线接在该端子上,极易造成人身安全事故。因此住宅装饰装修工程施工规范要求:连接开关、螺口灯具导线时,相线应先接开关,开关引出的相线应接在灯中心的端子上,零线应接在螺纹的端子上。
开关、插座安装问题: 1﹑开关不灵活或接触不良,插座插孔太松或太紧,影响了用户的正常使用。安全插座安全挡板损坏,起不到安全作用。进货时应认真检查,安装时或安装后发现不合格产品应及时更换,并应到有资质的部门进行检测。 2、住宅厨房、厕所内插座有的为普通插座。由于设计、施工的疏忽,给厨厕安装了普通插座,GB50327-2001中16.3.14条要求:厨房、卫生间应安装防溅插座。开关宜安装在门外开启侧的墙体上。在检查过程中也发现有的防溅插座未加橡胶垫,起不到其应有的作用,因此发现此问题应要求更换或补加橡胶垫。3、插座接线不符合规范要求,这一问题在工程中出现的较多。因此GB50303-2002中22.1.2条强制性条文要求:①单相两孔插座,面对插座的右孔或上孔与相线连接,左孔或下孔与零线连接;单相三孔插座,面对插座的右孔与相线连接,左孔与零线连接。②单相三孔、三相四孔及三相五孔插座的接地线接在上孔。插座的接地端子不与零线端子连接。同一场所的三相插座,接线的相序一致。③接地或接零线在插座间不串联连接。 结束语:它的存在是建筑工程质量的非常大的安全隐患,使广大居民在生活使用方面受到了極大的威胁。质量通病不容易消除,但它可以减小和控制。我们在整个施工过程中,要严格要求,按照规范标准进行操作,并加强管理,这样才可以消除或避免质量问题。