摘要:暖通空调设备是一个庞大而复杂的系统工程,大到跟大型的高层办公楼,星级酒店,小的直接跟民用的建筑有着重要的关系,其施工技术关系到管道工程以及图纸设计等关键技术,我们作为专业的暖通技术人员,必须严格把握好每道施工环节,保证建筑物的暖通系统正常使用。本文在此从施工中经常出现的一些问题出发,提出了实际施工过程中应该加强的几点解决措施。
关键词:暖通空调;安装施工;噪声
Abstract: HVAC equipment is a huge and complicated system engineering, large to large high-rise office building, Stars Hotel, small directly with the civil construction has an important relationship, the construction technology related to the pipeline engineering and design drawings and other key technologies, we as a professional HVAC technology personnel, must be strictly a good grasp of each construction link, to ensure the normal use of the building HVAC system. In this paper starting some problems frequently arise from the construction, we should strengthen the measures to solve some actual construction process.
Key words: HVAC installation construction; noise
中图分类号:TM925.12 文献标识码: 文章编号:
一、暖通空调安装概述
现在,暖通空调是人们所使用空调中最常用的一种,暖通空调以其独特的优势而独占市场。其将采暖、通风和空气调节三大功能结合在一起,并以能创造一种比一般的空调更舒适的室内环境而著称。随着科技的发展,家用空调器历经几代发展终不能满足人们日益增长的需要,不论是窗式空调器还是分体式家用空调器都只能解决冷暖问题而对空气处理过程束手无策,而暖通空调却以具有舒适、健康的特点逐渐得到人们的广泛亲睐。暖通空调施工是建筑施工中的一个重要分项,其的安装施工是一个极为复杂的工程,其施工问题直接影响着整个工程的质量和进度。通常所说的暖通空调设计主要包括制冷供暖系统设计、新风系统设计、排风系统设计等,其所涵盖的范围不仅仅是供暖这一个小范围,所以暖通空调安装工程的质量直接影响到建筑物的使用性能,要严格控制施工过程,保证安装质量。
二、暖通空调安装施工中普遍存在的问题
(一)管线、设备的定位和标高交叉方面
对于综合性的建筑物,吊顶空间内有空调末端设备、送回风管、排风管、冷冻水管、冷凝水管、喷淋管、消防管、电气桥架等专业管线。在图纸标注不足的情况下按图进行施工,往往是先安装的管道施工很方便,后安装的管道施工很困难,只能装在不该安装的位置或标高上,严重影响工程质量和进度。针对以上问题,必须遵守管线工程综合设计原则:
1、根据管道性能和用途的不同,建筑物中的管道大致可分为以下几类:(1)给水管道:包括生活给水、消防给水、生产用水等;(2)排水管道:包括生活污水、生活废水、消防排水、雨水、其他排水等;(3)中水管道:包括中水收集及中水供应;(4)热力管道:包括采暖、热水供应及空调空气处理设备中所需的蒸汽或热水;(5)燃气管道:有气体燃料、液体燃料之分;(6)空气管道:包括通风工程、空调系统中的各类风管,以及某些生產设备所需的压缩空气管;(7)供配电线路或电缆:包括动力配电、照明配电、弱电系统配电等,其中弱电部分包括共享电视天线、通信、广播及火灾报警及智能建筑系统等。
2、管线工程综合设计时各专业管线互相避让的原则如下:
(1)小管道避让大管道。因小管道造价低易安装;
(2)临时管线避让永久管线;
(3)新建管线避让原有管线;
(4)压力管道避让重力自流管道,因为对重力自流管道有坡度要求,不能随意抬高;
(5)金属管避让非金属管。因为金属管较容易弯曲、切割和连接;
(6)冷水管避让热水管。因为热水管往往需要做保温层,造价较高;
(7)低压管避让高压管。因为高压管造价高且安装要求高;
(8)空气管避让水管(指管径相近时)。因为水管更宜短且直。
(二)设备噪声超标方面
设备噪音主要来源于空调末端设备碰撞,噪声产生的原因主要是设计、安装产生,尤其是安装所产生的噪声不容忽视。暖通空调除自身专业外还涉及建筑、声乐、结构等各专业,噪声控制需要各专业相互间的协调配合。
(三)空调水系统水循环
水系统中央空调施工中最关键的环节,施工出现问题会直接影响系统正常运行。中央空调冷冻水系统最常见的问题是冷冻水系统管道循环不畅。造成管道循环不良的原因是:
1、管道因各专业管线交叉,施工中没有协调处理好,造成管网出现许多气囊,影响管网循环;
2、空调水系统管道清洗不干净,直接造成空调水系统堵塞。
(四)水凝结
空调系统在调试和运行中会出现结露滴水的现象,出现这一问题的原因可能是由于凝结水排水管的坡度小,或根本没有坡度而造成的漏水。或由于风机盘管的集水盘安装不平,或盘内排水口堵塞而盘水外溢。由于冷冻水管及阀门的保温质量差,保温层未贴紧冷冻水管壁,造成管道外壁空气冷凝水的滴水。还有的是集水盘下表面的二次凝结水滴水。因此管道安装和保温不良、管道与管件、管道与设备之间接触不严密、管道安装违法操作规程等都可能造成这一问题。管道、关键材料的优劣直接影响着安装的质量,所以在管材安装之前进行系统认真的检查是有必要的。
安装问题解决方案 暖通空调设备安装的施工问题通常为以上所提到的四个方面,当然在安装过程中经常还会出现各种复杂问题。下面就常见问题提出几点解决方案:
1、设备噪声超标处理
1.1设备安装
新风机、空调机安装采用弹簧阻尼减振器,风机与风管连接采用软连接,新风机组与水管采用软接头连接,风机盘管采用弹簧吊钩,风机盘管与水管采用软管连接。对空调机房进行吸音处理,比如在空调机房内采用隔声材料做成围护结构,以防止设备噪声外传,或在机房内贴吸声材料:采用凹凸型吸声板作为机房墙面或吊顶板,以增强吸声效果:机房应尽量减少设置门窗,且设置门窗应采用吸声门窗或吸声百叶窗,尽量减少设备噪声外传。
1.2水管安装
水管安装要严格执行国家规范,冷冻水主干管及冷却水管吊架要采用弹簧减振吊架,而且吊架不能固定在楼板上,应尽量固定在梁上,或在梁与梁之间架设槽钢横梁固定。水管穿过楼板或过墙必须采用套管,且套管与水管之间要用阻燃材料填封。
1.3风系统安装
风管制作安装要严格按照国家规范进行施工,在风机进出口安装阻抗消声器,新风进口处采用消声百叶,风管适当部位设置消声器,风管弯头部位设置消声弯头,空调和新风消声器的外部采用优质保温材料保温,与静压箱一样其内贴优质吸音材料。由于送酬风管均采用低风速、大风量以降低噪声,风管截面积比较大,如果风管安装强度及其整体刚度不够,就会产生摩擦及振动噪声。建议风管吊架尽可能采用橡胶减振垫,确保风管不产生振动噪声。
1.4冷冻水管主管支架安装
根据笔者多年来的工程安装经验发现噪音会沿冷冻主管传递,随着时间的推移,将会对设备运行带来一定的损害。经过研究、试验,对刚性支架做出改进,即在原主管刚性支架上加装弹簧减振器,使振动及噪音被在楼板与刚性支架之间的弹簧减振器有效消除。在笔者调查的某施工企业的几个工程施工中均采用了此工艺,并收到了良好的效果,故建议有关施工企业,在机房内的供回水主管、冷冻水主管也使用此工艺施工,消除噪音。
2、水凝结解决方法
2.1在设计管道时,管道的长度和坡度都应适宜,否则会出现滴水现象。管道的安装和布置要适合冷凝水的尽快排出,必要时可以设置水封装置。
2.2注重材料的保温。风管与冷冻水管必须注意保温,管道的保温必须把握好两个方面,一个是保证其完整性,另一个是密闭性。管道保温的完整性要求不允许出现冷损的存在的,一旦存在冷损的表面,都应该进行保温材料敷设隔热处理。而保温的密闭性则要求保证所以保温层面都不允许有任何破损,必须保证密封不透气。
3、严格控制材料质量
材料的采购受多方面的限制,比如工程造价、材料属性、施工难度等各个方面的影响,在选择的过程中需各方面权衡,达到质量和效益的最优。根据我国暖通空调方面材料采购的现状,现在市场上的材料质量参差不齐,以假乱真、以次充好的现象非常普遍,所以在材料设备的选购中应严格筛选,并且不能偷工减料,否则将会造成工程返工而不能如期完工或者質量水平严重下降。
4、严格控制施工过程
施工过程中管道支架的位置、标高、坡度都必须符合设计要求。在施工过程中,要保证坡度在准确的范围内,可以调整供暖干管或者填补管道漏洞空隙,此外应减小位置、标高和设计值的偏差。在施工中应尽量考虑各方面影响因素,严格按照章程和规范执行,并采用相关的工艺,遵循一定的原则,避免管道交叉严重、阻塞、结露漏水等问题。做好施工中的控制监督工作,减少错误出现的几率。
5、加强各专业间的配合
建筑施工是众多专业之间相互配合完成的,暖通空调设备施工也是如此。工艺对土建就有很强的要求,例如,在土建中需预留通风管道的孔洞;在风道竖井砌砖时应该采用水泥砂抹面;为排水方便应设排水沟或集水坑和排水泵等装置。诸如这些问题需在设计初期就尽量相互沟通,在施工前和施工图纸会审阶段就提出相应的预防措施。
总结
在暖通空调工程施工管理中,管理人员应细致地作好质量控制工作,空调工程施工前要了解设计意图,熟悉各专业施工图,编制好施工组织图,要抓住工程的控制要点,做好控制要点的事前、事中、事后管理。
关键词:暖通空调;安装施工;噪声
Abstract: HVAC equipment is a huge and complicated system engineering, large to large high-rise office building, Stars Hotel, small directly with the civil construction has an important relationship, the construction technology related to the pipeline engineering and design drawings and other key technologies, we as a professional HVAC technology personnel, must be strictly a good grasp of each construction link, to ensure the normal use of the building HVAC system. In this paper starting some problems frequently arise from the construction, we should strengthen the measures to solve some actual construction process.
Key words: HVAC installation construction; noise
中图分类号:TM925.12 文献标识码: 文章编号:
一、暖通空调安装概述
现在,暖通空调是人们所使用空调中最常用的一种,暖通空调以其独特的优势而独占市场。其将采暖、通风和空气调节三大功能结合在一起,并以能创造一种比一般的空调更舒适的室内环境而著称。随着科技的发展,家用空调器历经几代发展终不能满足人们日益增长的需要,不论是窗式空调器还是分体式家用空调器都只能解决冷暖问题而对空气处理过程束手无策,而暖通空调却以具有舒适、健康的特点逐渐得到人们的广泛亲睐。暖通空调施工是建筑施工中的一个重要分项,其的安装施工是一个极为复杂的工程,其施工问题直接影响着整个工程的质量和进度。通常所说的暖通空调设计主要包括制冷供暖系统设计、新风系统设计、排风系统设计等,其所涵盖的范围不仅仅是供暖这一个小范围,所以暖通空调安装工程的质量直接影响到建筑物的使用性能,要严格控制施工过程,保证安装质量。
二、暖通空调安装施工中普遍存在的问题
(一)管线、设备的定位和标高交叉方面
对于综合性的建筑物,吊顶空间内有空调末端设备、送回风管、排风管、冷冻水管、冷凝水管、喷淋管、消防管、电气桥架等专业管线。在图纸标注不足的情况下按图进行施工,往往是先安装的管道施工很方便,后安装的管道施工很困难,只能装在不该安装的位置或标高上,严重影响工程质量和进度。针对以上问题,必须遵守管线工程综合设计原则:
1、根据管道性能和用途的不同,建筑物中的管道大致可分为以下几类:(1)给水管道:包括生活给水、消防给水、生产用水等;(2)排水管道:包括生活污水、生活废水、消防排水、雨水、其他排水等;(3)中水管道:包括中水收集及中水供应;(4)热力管道:包括采暖、热水供应及空调空气处理设备中所需的蒸汽或热水;(5)燃气管道:有气体燃料、液体燃料之分;(6)空气管道:包括通风工程、空调系统中的各类风管,以及某些生產设备所需的压缩空气管;(7)供配电线路或电缆:包括动力配电、照明配电、弱电系统配电等,其中弱电部分包括共享电视天线、通信、广播及火灾报警及智能建筑系统等。
2、管线工程综合设计时各专业管线互相避让的原则如下:
(1)小管道避让大管道。因小管道造价低易安装;
(2)临时管线避让永久管线;
(3)新建管线避让原有管线;
(4)压力管道避让重力自流管道,因为对重力自流管道有坡度要求,不能随意抬高;
(5)金属管避让非金属管。因为金属管较容易弯曲、切割和连接;
(6)冷水管避让热水管。因为热水管往往需要做保温层,造价较高;
(7)低压管避让高压管。因为高压管造价高且安装要求高;
(8)空气管避让水管(指管径相近时)。因为水管更宜短且直。
(二)设备噪声超标方面
设备噪音主要来源于空调末端设备碰撞,噪声产生的原因主要是设计、安装产生,尤其是安装所产生的噪声不容忽视。暖通空调除自身专业外还涉及建筑、声乐、结构等各专业,噪声控制需要各专业相互间的协调配合。
(三)空调水系统水循环
水系统中央空调施工中最关键的环节,施工出现问题会直接影响系统正常运行。中央空调冷冻水系统最常见的问题是冷冻水系统管道循环不畅。造成管道循环不良的原因是:
1、管道因各专业管线交叉,施工中没有协调处理好,造成管网出现许多气囊,影响管网循环;
2、空调水系统管道清洗不干净,直接造成空调水系统堵塞。
(四)水凝结
空调系统在调试和运行中会出现结露滴水的现象,出现这一问题的原因可能是由于凝结水排水管的坡度小,或根本没有坡度而造成的漏水。或由于风机盘管的集水盘安装不平,或盘内排水口堵塞而盘水外溢。由于冷冻水管及阀门的保温质量差,保温层未贴紧冷冻水管壁,造成管道外壁空气冷凝水的滴水。还有的是集水盘下表面的二次凝结水滴水。因此管道安装和保温不良、管道与管件、管道与设备之间接触不严密、管道安装违法操作规程等都可能造成这一问题。管道、关键材料的优劣直接影响着安装的质量,所以在管材安装之前进行系统认真的检查是有必要的。
安装问题解决方案 暖通空调设备安装的施工问题通常为以上所提到的四个方面,当然在安装过程中经常还会出现各种复杂问题。下面就常见问题提出几点解决方案:
1、设备噪声超标处理
1.1设备安装
新风机、空调机安装采用弹簧阻尼减振器,风机与风管连接采用软连接,新风机组与水管采用软接头连接,风机盘管采用弹簧吊钩,风机盘管与水管采用软管连接。对空调机房进行吸音处理,比如在空调机房内采用隔声材料做成围护结构,以防止设备噪声外传,或在机房内贴吸声材料:采用凹凸型吸声板作为机房墙面或吊顶板,以增强吸声效果:机房应尽量减少设置门窗,且设置门窗应采用吸声门窗或吸声百叶窗,尽量减少设备噪声外传。
1.2水管安装
水管安装要严格执行国家规范,冷冻水主干管及冷却水管吊架要采用弹簧减振吊架,而且吊架不能固定在楼板上,应尽量固定在梁上,或在梁与梁之间架设槽钢横梁固定。水管穿过楼板或过墙必须采用套管,且套管与水管之间要用阻燃材料填封。
1.3风系统安装
风管制作安装要严格按照国家规范进行施工,在风机进出口安装阻抗消声器,新风进口处采用消声百叶,风管适当部位设置消声器,风管弯头部位设置消声弯头,空调和新风消声器的外部采用优质保温材料保温,与静压箱一样其内贴优质吸音材料。由于送酬风管均采用低风速、大风量以降低噪声,风管截面积比较大,如果风管安装强度及其整体刚度不够,就会产生摩擦及振动噪声。建议风管吊架尽可能采用橡胶减振垫,确保风管不产生振动噪声。
1.4冷冻水管主管支架安装
根据笔者多年来的工程安装经验发现噪音会沿冷冻主管传递,随着时间的推移,将会对设备运行带来一定的损害。经过研究、试验,对刚性支架做出改进,即在原主管刚性支架上加装弹簧减振器,使振动及噪音被在楼板与刚性支架之间的弹簧减振器有效消除。在笔者调查的某施工企业的几个工程施工中均采用了此工艺,并收到了良好的效果,故建议有关施工企业,在机房内的供回水主管、冷冻水主管也使用此工艺施工,消除噪音。
2、水凝结解决方法
2.1在设计管道时,管道的长度和坡度都应适宜,否则会出现滴水现象。管道的安装和布置要适合冷凝水的尽快排出,必要时可以设置水封装置。
2.2注重材料的保温。风管与冷冻水管必须注意保温,管道的保温必须把握好两个方面,一个是保证其完整性,另一个是密闭性。管道保温的完整性要求不允许出现冷损的存在的,一旦存在冷损的表面,都应该进行保温材料敷设隔热处理。而保温的密闭性则要求保证所以保温层面都不允许有任何破损,必须保证密封不透气。
3、严格控制材料质量
材料的采购受多方面的限制,比如工程造价、材料属性、施工难度等各个方面的影响,在选择的过程中需各方面权衡,达到质量和效益的最优。根据我国暖通空调方面材料采购的现状,现在市场上的材料质量参差不齐,以假乱真、以次充好的现象非常普遍,所以在材料设备的选购中应严格筛选,并且不能偷工减料,否则将会造成工程返工而不能如期完工或者質量水平严重下降。
4、严格控制施工过程
施工过程中管道支架的位置、标高、坡度都必须符合设计要求。在施工过程中,要保证坡度在准确的范围内,可以调整供暖干管或者填补管道漏洞空隙,此外应减小位置、标高和设计值的偏差。在施工中应尽量考虑各方面影响因素,严格按照章程和规范执行,并采用相关的工艺,遵循一定的原则,避免管道交叉严重、阻塞、结露漏水等问题。做好施工中的控制监督工作,减少错误出现的几率。
5、加强各专业间的配合
建筑施工是众多专业之间相互配合完成的,暖通空调设备施工也是如此。工艺对土建就有很强的要求,例如,在土建中需预留通风管道的孔洞;在风道竖井砌砖时应该采用水泥砂抹面;为排水方便应设排水沟或集水坑和排水泵等装置。诸如这些问题需在设计初期就尽量相互沟通,在施工前和施工图纸会审阶段就提出相应的预防措施。
总结
在暖通空调工程施工管理中,管理人员应细致地作好质量控制工作,空调工程施工前要了解设计意图,熟悉各专业施工图,编制好施工组织图,要抓住工程的控制要点,做好控制要点的事前、事中、事后管理。