摘要:国内建筑业发展非常迅速,随着《高层民用建筑设计防火规范》(以下简称《高规》)的更新及新《自动喷水灭火系统设计规范》(以下简称《自喷规范》)的出台,对高层建筑消防给排水设计的要求也日趋严格。特别是近年来,各省、市都先后开始实施建筑工程图审查制度,其审查的主要依据为2000 年颁布的《工程建设标准强制性条文》,《强制性条文》所规定的各项条款是设计当中必须遵循的硬性要求。
关键词:建筑消防;给排水设计;问题措施
Abstract: the domestic construction industry is developing very fast, with the code for fire protection design of high civil buildings (hereinafter referred to as the high rules ") and the renewal of the new "automatic sprinkler system design rules" (hereinafter referred to as the spray from the standard "), the promulgation of the fire water supply and drainage design of high-rise building requirements are strictly. Especially in recent years, province and city are successively began to carry out the system of review of architecture engineering drawings, the review of the main basis for 2000 years "issued by the engineering construction standards mandatory provisions", "the mandatory provisions of the regulations of the terms is design must be in accordance with the requirements of the rigid.
Keywords: building fire; Water supply and drainage design; Problem measures
中圖分类号:S611 文献标识码:A文章编号:
1 在高层建筑内应控制使用双阀双出口消火栓代替两组单阀消火栓
《高规》规定“同层相邻两个消火栓的水枪的充实水柱达到被保护范围内的任何部位。”在某些条形高层建筑中,其端部是否可以采用双阀双出口消火栓,从而省去1 组单阀消火栓的设置呢?虽然在中国建筑工业出版社出版的《给水排水设计手册》(第二版) 中提出“在每层楼的端部可采用双阀双出口消火栓”,但是《高规》中明确规定“十八层及十八层以下,每层不超过8 户、建筑面积不超过650m2 的塔式住宅,当设两根消防竖管。有困难时,可设一根竖管,但必须采用双阀双出口消火栓。”且以强制性条文的形式予以规定。因此,在设计中我们应该力求避免出现这种情况。
2 正确计算消火栓充实水柱长度,合理布置消火栓
《高规》规定“消火栓的水枪充实水柱应通过水力计算确定,且建筑高度不超过100m 的高层建筑不应小于10m;建筑高度超过100m 的高层建筑不应小于13m。”对于建筑高度不超过100m 的高层建筑,设计中我们可以根据水枪最小流量5L/s,水枪喷嘴口径19mm,查有关设计手册得出水枪充实水柱长度为11.3m;对于建筑高度超过100m 的高层建筑,我们可以调整水枪流量以达到满足规范所需要水枪充实水柱长度。而在实际中,高层建筑标准楼层净高考虑经济因素一般控制在4.0m 以下,如果根据公式Sk= (H1-H2) /SINα 计算水枪充实水柱,当层高取4m,水枪上倾角取45°时,计算Sk 为4.24m,远远达不到规范要求,即层高限制了充实水柱的长度。但是,我们可以调整水枪上倾角来达到提高充实水柱长度的目的,因为规范及有关手册提出水枪上倾角不应大于60°,并未规定其下限角度值。通过计算,当层高仍旧取4m,充实水柱取11.3m 时,水枪上倾角为14.87°。况且《高规》有关条文说明解释道,口径19mm 水枪的充实水柱小于10m 时,由于火场烟雾大,辐射热高,扑救火灾有一定困难,所以水枪的充实水柱长度首先应该计算,同时又要满足《高规》规定各种高层建筑水枪的充实水柱下限值。按照水枪充实水柱长度,可以确定消火栓保护半径,但是在设计中我们不能简单的用保护半径画圆来布置消火栓。因为高层建筑平面中隔墙、内走道、门的布置会影响消火栓的使用,设计中应该用水龙带长度、充实水柱的水平投影去校核消火栓保护半径最远点。
3 正确设置消防水池及保证高层建筑两路供水
通常在高层建筑中,在市政供水不能满足消防用水量要求或市政为单路进水时,规范都要求设置消防水池。计算消防水池容积时,应将火灾延续时间内室内各消防用水量之和减去市政进水管的补水量。补水时间可按最长的火灾延续时间计。如果要考虑室外消防用水量或是设置生活、消防共用水池,则还需要补充相应的用水量。当设置生活、消防共用水池时,不能利用建筑物的本体结构做水池池壁以及池底,以防止生活水质污染。对此, 《强制性条文》中已经明令禁止。同理,如果高层建筑屋顶设有生活、消防共用水箱,也应满足该要求。从消防水池接入水泵间的引入管应该保证不少于2 根,如果在接入泵房前就将引入管汇合为一,对消防水池而言,仅为单路供水,存在供水的安全隐患。同时,从消防水泵接入各消防管网的供水管也应保证两路。
4 高层建筑消防电梯间前室必须设消火栓
《高规》规定“高层建筑消防电梯间前室必须设消火栓”,那么设于前室的消火栓可否保护相邻部位呢? 《高规》的条文说明对此并没有具体说明,但是《建筑设计防火规范》中对“消防电梯前室应设室内消火栓”的条文说明中明确指出:消防电梯前室内消火栓是为便于消防队员使用消火栓并开辟通路,不能计入总消火栓数内。因此在设计中我们通常将其视为消防电梯间前室专用,而不保护其余部位。
5 消防水泵出口处的放水阀和稳压回流措施
《高规》规定“消防水泵的供水管上应设置DN65 的放水阀门”,目的是便于水泵检查试验时排水。排水量小时,可直接排至泵房集水池;排水量大时,可排回消防水池。同时,消防水泵出口还需要考虑一定的稳压回流措施。因为在实际使用中,会出现消防水量小于水泵选定流量值的情况,此时水泵扬程远大于设计值,在无任何回流措施保护下,消防管网压力过大,容易造成事故。简单的做法是在供水管上装设安全稳压阀,在管网超压时,可以通过回流管泄压,将回流水排至消防水池;在管网压力不稳定时,亦可稳压。
6 高层建筑部分层自喷配水管入口应按要求减压
新《自喷规范》规定:“管道直径应经水力计算确定。配水管道的布置,应使配水管入口的压力均衡。轻危险级、中危险级场所中各配水管入口的压力均不宜大于0.4MPa。”而老《自喷规范》对此并无具体要求。高层民用建筑火灾危险等级一般为中危险级,自喷水泵是根据最高层最不利喷头工作压力经过计算而选择。计算的最不利层配水管入口处所需压力均不大于0.3MPa (最不利喷头工作压力按0.05MPa 计),由于自喷水泵的扬程还需考虑建筑高度、水力损失等因素,故必使高层建筑的底部几层配水管入口处压力大于0.4MPa。因而在设计时,在自喷水泵扬程的确定上不能一味放大了事,应该在自喷平面布置完毕后通过水力计算校核水泵扬程,并在此基础上校核底部几层配水管入口处压力。
7 正确设置自喷末端试水装置,解决末端试水装置排水问题
《自喷规范》要求“每个报警阀组控制的最不利点喷头处,应设置末端试水装置,末端试水装置的出水,应采取孔口出流的方式排入排水管道。”在设计中,我们通常不会忘记末端试水装置中试水阀、压力表的设置,但是往往忽视试水接头的设置,特别是试水接头出水口的口径没有交代。其实目前市场许多消防设备生产厂家,可以生产成套的末端试水装置(ZSPP 末端试水装置,含试水阀、压力表、试水接头),我们只需要根据设计要求,按照试水接头出水口的流量系数选择定型产品即可。此外,试水接头不能与管道或软管直接连接,影响孔口出流的效果;自喷排水管也应设计成间接排放,以免下水道气体通过排水漏斗散入室内,影响室内空气品质。
8 消防增压泵的设置问题
为保证《高规》或《自喷规范》要求的最高层消火栓或喷头的静压力值,在高位水箱的水位差不够的情况下,设计中我们一般在高位水箱处设置消防增压泵。首先,增压泵的流量要满足1 股水柱或1 个喷头的水量;其次,增压泵的扬程不宜过大。由于高位水箱消防水位与顶层消火栓或喷头已有一定的位差,规范要求的静压力值减去这个水位差就是增压泵的最小扬程,所以增压泵的扬程一般只需要几米足以满足要求。如果增压泵扬程选的过大,将导致下层管网承压过高,消火栓出口压力或是各层自喷配水干管入口处压力增大,均需采取减压措施,使消防系统复杂化。但是仅靠增压泵来满足消防静压要求也不合适,因为增压泵的运行由压力传感信号控制向消防系统不断打水以维持压力,水泵需要常年频繁启停,机件容易损坏。故在条件允许的情况下,与建筑协商适当抬高水箱位置,利用高位水箱稳压最为稳妥;建筑条件实在不允许时,设计选择带气压水罐的增压设施亦可。
关键词:建筑消防;给排水设计;问题措施
Abstract: the domestic construction industry is developing very fast, with the code for fire protection design of high civil buildings (hereinafter referred to as the high rules ") and the renewal of the new "automatic sprinkler system design rules" (hereinafter referred to as the spray from the standard "), the promulgation of the fire water supply and drainage design of high-rise building requirements are strictly. Especially in recent years, province and city are successively began to carry out the system of review of architecture engineering drawings, the review of the main basis for 2000 years "issued by the engineering construction standards mandatory provisions", "the mandatory provisions of the regulations of the terms is design must be in accordance with the requirements of the rigid.
Keywords: building fire; Water supply and drainage design; Problem measures
中圖分类号:S611 文献标识码:A文章编号:
1 在高层建筑内应控制使用双阀双出口消火栓代替两组单阀消火栓
《高规》规定“同层相邻两个消火栓的水枪的充实水柱达到被保护范围内的任何部位。”在某些条形高层建筑中,其端部是否可以采用双阀双出口消火栓,从而省去1 组单阀消火栓的设置呢?虽然在中国建筑工业出版社出版的《给水排水设计手册》(第二版) 中提出“在每层楼的端部可采用双阀双出口消火栓”,但是《高规》中明确规定“十八层及十八层以下,每层不超过8 户、建筑面积不超过650m2 的塔式住宅,当设两根消防竖管。有困难时,可设一根竖管,但必须采用双阀双出口消火栓。”且以强制性条文的形式予以规定。因此,在设计中我们应该力求避免出现这种情况。
2 正确计算消火栓充实水柱长度,合理布置消火栓
《高规》规定“消火栓的水枪充实水柱应通过水力计算确定,且建筑高度不超过100m 的高层建筑不应小于10m;建筑高度超过100m 的高层建筑不应小于13m。”对于建筑高度不超过100m 的高层建筑,设计中我们可以根据水枪最小流量5L/s,水枪喷嘴口径19mm,查有关设计手册得出水枪充实水柱长度为11.3m;对于建筑高度超过100m 的高层建筑,我们可以调整水枪流量以达到满足规范所需要水枪充实水柱长度。而在实际中,高层建筑标准楼层净高考虑经济因素一般控制在4.0m 以下,如果根据公式Sk= (H1-H2) /SINα 计算水枪充实水柱,当层高取4m,水枪上倾角取45°时,计算Sk 为4.24m,远远达不到规范要求,即层高限制了充实水柱的长度。但是,我们可以调整水枪上倾角来达到提高充实水柱长度的目的,因为规范及有关手册提出水枪上倾角不应大于60°,并未规定其下限角度值。通过计算,当层高仍旧取4m,充实水柱取11.3m 时,水枪上倾角为14.87°。况且《高规》有关条文说明解释道,口径19mm 水枪的充实水柱小于10m 时,由于火场烟雾大,辐射热高,扑救火灾有一定困难,所以水枪的充实水柱长度首先应该计算,同时又要满足《高规》规定各种高层建筑水枪的充实水柱下限值。按照水枪充实水柱长度,可以确定消火栓保护半径,但是在设计中我们不能简单的用保护半径画圆来布置消火栓。因为高层建筑平面中隔墙、内走道、门的布置会影响消火栓的使用,设计中应该用水龙带长度、充实水柱的水平投影去校核消火栓保护半径最远点。
3 正确设置消防水池及保证高层建筑两路供水
通常在高层建筑中,在市政供水不能满足消防用水量要求或市政为单路进水时,规范都要求设置消防水池。计算消防水池容积时,应将火灾延续时间内室内各消防用水量之和减去市政进水管的补水量。补水时间可按最长的火灾延续时间计。如果要考虑室外消防用水量或是设置生活、消防共用水池,则还需要补充相应的用水量。当设置生活、消防共用水池时,不能利用建筑物的本体结构做水池池壁以及池底,以防止生活水质污染。对此, 《强制性条文》中已经明令禁止。同理,如果高层建筑屋顶设有生活、消防共用水箱,也应满足该要求。从消防水池接入水泵间的引入管应该保证不少于2 根,如果在接入泵房前就将引入管汇合为一,对消防水池而言,仅为单路供水,存在供水的安全隐患。同时,从消防水泵接入各消防管网的供水管也应保证两路。
4 高层建筑消防电梯间前室必须设消火栓
《高规》规定“高层建筑消防电梯间前室必须设消火栓”,那么设于前室的消火栓可否保护相邻部位呢? 《高规》的条文说明对此并没有具体说明,但是《建筑设计防火规范》中对“消防电梯前室应设室内消火栓”的条文说明中明确指出:消防电梯前室内消火栓是为便于消防队员使用消火栓并开辟通路,不能计入总消火栓数内。因此在设计中我们通常将其视为消防电梯间前室专用,而不保护其余部位。
5 消防水泵出口处的放水阀和稳压回流措施
《高规》规定“消防水泵的供水管上应设置DN65 的放水阀门”,目的是便于水泵检查试验时排水。排水量小时,可直接排至泵房集水池;排水量大时,可排回消防水池。同时,消防水泵出口还需要考虑一定的稳压回流措施。因为在实际使用中,会出现消防水量小于水泵选定流量值的情况,此时水泵扬程远大于设计值,在无任何回流措施保护下,消防管网压力过大,容易造成事故。简单的做法是在供水管上装设安全稳压阀,在管网超压时,可以通过回流管泄压,将回流水排至消防水池;在管网压力不稳定时,亦可稳压。
6 高层建筑部分层自喷配水管入口应按要求减压
新《自喷规范》规定:“管道直径应经水力计算确定。配水管道的布置,应使配水管入口的压力均衡。轻危险级、中危险级场所中各配水管入口的压力均不宜大于0.4MPa。”而老《自喷规范》对此并无具体要求。高层民用建筑火灾危险等级一般为中危险级,自喷水泵是根据最高层最不利喷头工作压力经过计算而选择。计算的最不利层配水管入口处所需压力均不大于0.3MPa (最不利喷头工作压力按0.05MPa 计),由于自喷水泵的扬程还需考虑建筑高度、水力损失等因素,故必使高层建筑的底部几层配水管入口处压力大于0.4MPa。因而在设计时,在自喷水泵扬程的确定上不能一味放大了事,应该在自喷平面布置完毕后通过水力计算校核水泵扬程,并在此基础上校核底部几层配水管入口处压力。
7 正确设置自喷末端试水装置,解决末端试水装置排水问题
《自喷规范》要求“每个报警阀组控制的最不利点喷头处,应设置末端试水装置,末端试水装置的出水,应采取孔口出流的方式排入排水管道。”在设计中,我们通常不会忘记末端试水装置中试水阀、压力表的设置,但是往往忽视试水接头的设置,特别是试水接头出水口的口径没有交代。其实目前市场许多消防设备生产厂家,可以生产成套的末端试水装置(ZSPP 末端试水装置,含试水阀、压力表、试水接头),我们只需要根据设计要求,按照试水接头出水口的流量系数选择定型产品即可。此外,试水接头不能与管道或软管直接连接,影响孔口出流的效果;自喷排水管也应设计成间接排放,以免下水道气体通过排水漏斗散入室内,影响室内空气品质。
8 消防增压泵的设置问题
为保证《高规》或《自喷规范》要求的最高层消火栓或喷头的静压力值,在高位水箱的水位差不够的情况下,设计中我们一般在高位水箱处设置消防增压泵。首先,增压泵的流量要满足1 股水柱或1 个喷头的水量;其次,增压泵的扬程不宜过大。由于高位水箱消防水位与顶层消火栓或喷头已有一定的位差,规范要求的静压力值减去这个水位差就是增压泵的最小扬程,所以增压泵的扬程一般只需要几米足以满足要求。如果增压泵扬程选的过大,将导致下层管网承压过高,消火栓出口压力或是各层自喷配水干管入口处压力增大,均需采取减压措施,使消防系统复杂化。但是仅靠增压泵来满足消防静压要求也不合适,因为增压泵的运行由压力传感信号控制向消防系统不断打水以维持压力,水泵需要常年频繁启停,机件容易损坏。故在条件允许的情况下,与建筑协商适当抬高水箱位置,利用高位水箱稳压最为稳妥;建筑条件实在不允许时,设计选择带气压水罐的增压设施亦可。