摘要:目前热水采暖广泛用于工业和民用建筑中,但是由于施工作业人员在热水采暖系统的施工、调整与运行管理方面的经验不足,系统在运行时可能会出现一些故障,影响正常供热。本文主要分析了热水采暖系统不热的原因,具体从设计、施工及运行管理三个方面对其进行了深入论述,并提出了一些相应的改进措施,可供施工人员参考。
关键词:设计; 施工; 运行管理; 散热器;
Abstract: At present, the hot water heating widely used in industrial and civil building, but because the construction work personnel in the hot water heating system construction, adjust and operation management experience, system in operation may appear some fault, affect the normal heating. This paper mainly analyzes the hot water heating system is not the cause of the heat, and the specific from design, construction and operation management of the three aspects of its further discussed, and puts forward some corresponding improvement measures for construction personnel reference.
Key Words: design; construction; operation management; radiator
中图分类号:S611 文献标识码:A 文章编号
前言
近年来热水采暖以其在技术和经济上的显著优越性得到广大用户的青睐。目前热水采暖广泛用于工业和民用建筑中。但是由于设计、施工作业人员在热水采暖系统的设计、施工、调整与运行管理方面的经验不足,系统在运行时可能会出现一些故障,影响正常供热。本文主要论述了热水采暖系统不热的常见原因及解决方法, 仅供同类工程参考。
一、设计方面分析
1、热媒设计参数定得过低。高层建筑物在以热水为媒介的热水采暖中, 由于锅炉承压能力所限, 锅炉输出的水( 约为 90℃ ) 不能直接送到供暖点的散热器, 只能通过换热设备。而换热设备的出水温度只有 70℃ 左右,设计人员把热媒定为 70℃ 或 55℃ , 这就明显地影响了传热效果。为了加大散热量, 势必得增加散热器的片数, 从实际运行情况来看, 散热面积的增加将进一步造成运行时热媒参数降得更低, 如此便形成恶性循環, 导致暖气散热量不够, 保证不了供暖室温要求。
2、循环方式选择不当, 造成严重水力失调。管路系统运行水力平衡直接影响供暖效果的好坏, 有时设计的散热器装了不少, 但效果很差, 有一部分设计人员没有进行水力平衡计算, 而又选择了异程的上供下回单管顺序式供热程式,以致造成了严重的水力失调。按设计要求, 热水采暖的各个并联环路的计算压力损失相对差额应不大于 15%, 这样的误差仅靠阀门调节很难奏效, 从而使有些立管流量比实际要求要小得多,立管所带的散热器当然不热。
3、散热器选型不当。散热器的选择要求散热效果好、体形小、有一定的承压能力、抗腐蚀能力强、便于清扫、尽量与建筑相匹配及美观大方等。各种散热器都有其自身的特点,目前, 市场上销售的散热器种类繁多, 设计人员可根据设计要求和实际运行情况选择适当的散热器。但是, 有些设计人员对散热器的特点缺乏了解, 选用了与实际情况相差甚远的散热器, 造成散热器效果不理想, 从而达不到设计要求的散热量, 应引起高度重视。
二、施工方面分析
1、施工人员未按图纸设计要求的设备及材料安装。施工人员出于经济考虑, 以劣质产品代替合格产品, 以同类产品中价格低的产品代替价格高的产品, 甚至错装漏装。例如,设计中选用的是截止阀, 而安装的却是闸板阀, 有些部位有阀门,而安装时却没有阀门, 在安装施工中, 以劣质散热器代替设计选用的散热器, 从而造成散热量不足, 无法满足室内温度标准要求。
2、施工队伍素质差, 出现安装技术失误。目前, 建筑市场从事安装工作的人员很大一部分是非专业,有的根本无法看懂图纸, 在有些关键部位中随意安装, 造成系统不热, 以下通过一个事例对其进行分析。事例: 机械循环系统中供水干管、回水干管及横支管坡度应为 0. 2% ~ 0. 3% , 有些工程施工人员不懂坡向的含义, 安装中出现无坡或倒坡现象致使系统排水不畅, 管道不热。施工队伍的素质问题是影响施工技术的关键因素之一。这一点一定要引起我们的高度重视。
三、运行管理方面分析
1、用户私自增加暖气片数。有些用户误认为散热器片数越多越好, 所以拼命私自增加自己住房的散热器片数, 却不知道增加后会造成整个系统水力失调,水流量减少, 室内反而不热。尤其对于上供下回的单立管系统, 如果上层增加了散热器片数, 下层的供水温度就会下降, 传热效果也会相应降低, 达不到要求的传热量, 收不到正常的采暖效果。
2、加盖暖气罩。现在大部分房子都进行了装修, 为了美观, 在暖气片外面加罩, 甚至把暖气片全封闭起来, 这样, 对传热效果十分不利。暖气片要把它的热量传给室内, 主要是通过空气对流来实现的, 而把暖气片封闭起来, 使得空气无法形成对流, 传热效果大大降低。
3、放气阀排气不畅。由于管理人员没有及时进行采暖管道的检查和保养, 有些采暖系统开始运行时能正常运行, 待运行一段时间后突然不热, 很可能是由于放气阀锈蚀等原因无法开启, 造成系统排气不畅, 影响其正常工作。有时, 同一组暖气半边热而另半边不热, 这也多是由于半边充气的缘故。
四、运行调试与检查验收方面分析
由于设计系统中的温差和实际安装过程中的水平管和立管阀门的开启情况, 常会造成有些管道阻力减少, 使得管道水力不平衡, 从而影响供暖效果。为了解决这一问题, 常用调节干管上的手动调节阀和立管上的截止阀来达到这一目的, 有些工程在交工时, 正好处在非采暖季节, 当时没有条件进行打压调试, 工程验收时也常常因为采暖属于辅助工程而被忽视, 未按《采暖施工与验收规范》进行详细和严格的验收, 而到了采暖季节, 系统开始运行时, 出现了问题, 所以每个采暖安装工程在施工完毕后, 一定要进行严格的运行调试, 使各个环路的压力损失误差不能超过设计规范的要求。运行调试是一个复杂的技术问题, 因为阀门多, 各阀门在管路中所处的位置不同, 调节的程度和次序非常重要, 所以在交工时, 建设单位一定要请有关专家协作验收, 只有这样才能保证系统在最佳工况条件下运行, 从而保证供暖效果。
五、具体的改进措施分析
1、设计方面。设计人员应尽量设计易于平衡、对称的供暖系统, 对较复杂的采暖情况(如多功能楼房的采暖设计) 一定要进行详细的水力平衡计算, 对所选择的散热器性能应有详细的了解, 尤其是对散热的可靠性要做调查研究, 不能偏信推销商的介绍。
2、施工方面。要发挥监理单位的监督作用, 以确保安装按设计图纸进行,提高安装质量, 一定要对安装的设备、材料进行验收, 发挥甲方代表的监督管理作用。同时, 施工完毕后应进行严格的运行调试,以保证采暖系统安全运行。
3、运行管理方面。一定要指派懂行的专家对要交工的工程按验收规范进行详细的验收, 不能流于形式, 对不合格的地方一定要进行整改,整改之后再进行验收, 直到完全合格。对用户进行常识教育, 多加宣传, 对有私自增加暖气片数和改变管道走向的用户要有严厉的惩罚措施, 房管部门或物业管理单位要加强对系统的维护保养, 勤检查、勤维修, 保证其整个供暖工作的正常运行。
六、结语
随着科学技术的进一步发展,热水采暖技术会不断提高、采暖设施会不断完善,从而给人们工作和生活场所提供一个舒适的环境,保证人体健康,促进我国现代化的发展。能源问题是一个关系到国计民生的大问题。目前在全国的各个领域中已广泛展开了节约能源的运动。对于正在迅速发展的供热事业来说,节约能源更为重要。因为供热企业是直接消耗能源为社会服务的,在这个企业中能源的消耗和合理使用,不但直接影响着企业的供热质量,而且直接关系到企业的生存和热用户(单位和个人)的经济利益以及承受能力。热水供暖系统不热是采暖地区较常见的一种情况, 并给人们的生活与工作造成了一定的影响。为了分析原因以找出正确的解决办法, 文中分别从设计、施工及运行管理三方面对其进行了系统的阐述, 并在此基础上提出了一些改进措施, 可为实际施工与设计提供参考。
参考文献:
[ 1] 贺 平, 孙 刚. 供热工程[ M] . 北京: 中国建筑工业出版社, 1993.
[ 2] 杨志宽. 钢制散热器腐蚀与控制 [ J] . 暖通空调, 2001, 31( 1) :21- 24.
[ 3] 陆耀庆. 供暖通风设计手册[ M ] . 北京: 中国建筑工业出版社 ,1987.
[ 4] 张俊红 , 韩 非. 立式直混换热器在供暖系统中的应用分析[ J] . 暖通空调, 2002, 32( 5) : 119- 120.
关键词:设计; 施工; 运行管理; 散热器;
Abstract: At present, the hot water heating widely used in industrial and civil building, but because the construction work personnel in the hot water heating system construction, adjust and operation management experience, system in operation may appear some fault, affect the normal heating. This paper mainly analyzes the hot water heating system is not the cause of the heat, and the specific from design, construction and operation management of the three aspects of its further discussed, and puts forward some corresponding improvement measures for construction personnel reference.
Key Words: design; construction; operation management; radiator
中图分类号:S611 文献标识码:A 文章编号
前言
近年来热水采暖以其在技术和经济上的显著优越性得到广大用户的青睐。目前热水采暖广泛用于工业和民用建筑中。但是由于设计、施工作业人员在热水采暖系统的设计、施工、调整与运行管理方面的经验不足,系统在运行时可能会出现一些故障,影响正常供热。本文主要论述了热水采暖系统不热的常见原因及解决方法, 仅供同类工程参考。
一、设计方面分析
1、热媒设计参数定得过低。高层建筑物在以热水为媒介的热水采暖中, 由于锅炉承压能力所限, 锅炉输出的水( 约为 90℃ ) 不能直接送到供暖点的散热器, 只能通过换热设备。而换热设备的出水温度只有 70℃ 左右,设计人员把热媒定为 70℃ 或 55℃ , 这就明显地影响了传热效果。为了加大散热量, 势必得增加散热器的片数, 从实际运行情况来看, 散热面积的增加将进一步造成运行时热媒参数降得更低, 如此便形成恶性循環, 导致暖气散热量不够, 保证不了供暖室温要求。
2、循环方式选择不当, 造成严重水力失调。管路系统运行水力平衡直接影响供暖效果的好坏, 有时设计的散热器装了不少, 但效果很差, 有一部分设计人员没有进行水力平衡计算, 而又选择了异程的上供下回单管顺序式供热程式,以致造成了严重的水力失调。按设计要求, 热水采暖的各个并联环路的计算压力损失相对差额应不大于 15%, 这样的误差仅靠阀门调节很难奏效, 从而使有些立管流量比实际要求要小得多,立管所带的散热器当然不热。
3、散热器选型不当。散热器的选择要求散热效果好、体形小、有一定的承压能力、抗腐蚀能力强、便于清扫、尽量与建筑相匹配及美观大方等。各种散热器都有其自身的特点,目前, 市场上销售的散热器种类繁多, 设计人员可根据设计要求和实际运行情况选择适当的散热器。但是, 有些设计人员对散热器的特点缺乏了解, 选用了与实际情况相差甚远的散热器, 造成散热器效果不理想, 从而达不到设计要求的散热量, 应引起高度重视。
二、施工方面分析
1、施工人员未按图纸设计要求的设备及材料安装。施工人员出于经济考虑, 以劣质产品代替合格产品, 以同类产品中价格低的产品代替价格高的产品, 甚至错装漏装。例如,设计中选用的是截止阀, 而安装的却是闸板阀, 有些部位有阀门,而安装时却没有阀门, 在安装施工中, 以劣质散热器代替设计选用的散热器, 从而造成散热量不足, 无法满足室内温度标准要求。
2、施工队伍素质差, 出现安装技术失误。目前, 建筑市场从事安装工作的人员很大一部分是非专业,有的根本无法看懂图纸, 在有些关键部位中随意安装, 造成系统不热, 以下通过一个事例对其进行分析。事例: 机械循环系统中供水干管、回水干管及横支管坡度应为 0. 2% ~ 0. 3% , 有些工程施工人员不懂坡向的含义, 安装中出现无坡或倒坡现象致使系统排水不畅, 管道不热。施工队伍的素质问题是影响施工技术的关键因素之一。这一点一定要引起我们的高度重视。
三、运行管理方面分析
1、用户私自增加暖气片数。有些用户误认为散热器片数越多越好, 所以拼命私自增加自己住房的散热器片数, 却不知道增加后会造成整个系统水力失调,水流量减少, 室内反而不热。尤其对于上供下回的单立管系统, 如果上层增加了散热器片数, 下层的供水温度就会下降, 传热效果也会相应降低, 达不到要求的传热量, 收不到正常的采暖效果。
2、加盖暖气罩。现在大部分房子都进行了装修, 为了美观, 在暖气片外面加罩, 甚至把暖气片全封闭起来, 这样, 对传热效果十分不利。暖气片要把它的热量传给室内, 主要是通过空气对流来实现的, 而把暖气片封闭起来, 使得空气无法形成对流, 传热效果大大降低。
3、放气阀排气不畅。由于管理人员没有及时进行采暖管道的检查和保养, 有些采暖系统开始运行时能正常运行, 待运行一段时间后突然不热, 很可能是由于放气阀锈蚀等原因无法开启, 造成系统排气不畅, 影响其正常工作。有时, 同一组暖气半边热而另半边不热, 这也多是由于半边充气的缘故。
四、运行调试与检查验收方面分析
由于设计系统中的温差和实际安装过程中的水平管和立管阀门的开启情况, 常会造成有些管道阻力减少, 使得管道水力不平衡, 从而影响供暖效果。为了解决这一问题, 常用调节干管上的手动调节阀和立管上的截止阀来达到这一目的, 有些工程在交工时, 正好处在非采暖季节, 当时没有条件进行打压调试, 工程验收时也常常因为采暖属于辅助工程而被忽视, 未按《采暖施工与验收规范》进行详细和严格的验收, 而到了采暖季节, 系统开始运行时, 出现了问题, 所以每个采暖安装工程在施工完毕后, 一定要进行严格的运行调试, 使各个环路的压力损失误差不能超过设计规范的要求。运行调试是一个复杂的技术问题, 因为阀门多, 各阀门在管路中所处的位置不同, 调节的程度和次序非常重要, 所以在交工时, 建设单位一定要请有关专家协作验收, 只有这样才能保证系统在最佳工况条件下运行, 从而保证供暖效果。
五、具体的改进措施分析
1、设计方面。设计人员应尽量设计易于平衡、对称的供暖系统, 对较复杂的采暖情况(如多功能楼房的采暖设计) 一定要进行详细的水力平衡计算, 对所选择的散热器性能应有详细的了解, 尤其是对散热的可靠性要做调查研究, 不能偏信推销商的介绍。
2、施工方面。要发挥监理单位的监督作用, 以确保安装按设计图纸进行,提高安装质量, 一定要对安装的设备、材料进行验收, 发挥甲方代表的监督管理作用。同时, 施工完毕后应进行严格的运行调试,以保证采暖系统安全运行。
3、运行管理方面。一定要指派懂行的专家对要交工的工程按验收规范进行详细的验收, 不能流于形式, 对不合格的地方一定要进行整改,整改之后再进行验收, 直到完全合格。对用户进行常识教育, 多加宣传, 对有私自增加暖气片数和改变管道走向的用户要有严厉的惩罚措施, 房管部门或物业管理单位要加强对系统的维护保养, 勤检查、勤维修, 保证其整个供暖工作的正常运行。
六、结语
随着科学技术的进一步发展,热水采暖技术会不断提高、采暖设施会不断完善,从而给人们工作和生活场所提供一个舒适的环境,保证人体健康,促进我国现代化的发展。能源问题是一个关系到国计民生的大问题。目前在全国的各个领域中已广泛展开了节约能源的运动。对于正在迅速发展的供热事业来说,节约能源更为重要。因为供热企业是直接消耗能源为社会服务的,在这个企业中能源的消耗和合理使用,不但直接影响着企业的供热质量,而且直接关系到企业的生存和热用户(单位和个人)的经济利益以及承受能力。热水供暖系统不热是采暖地区较常见的一种情况, 并给人们的生活与工作造成了一定的影响。为了分析原因以找出正确的解决办法, 文中分别从设计、施工及运行管理三方面对其进行了系统的阐述, 并在此基础上提出了一些改进措施, 可为实际施工与设计提供参考。