故障现象:在接入正常市电的情况下,每次打开UPS,便听到继电器“吱吱”反复的动作声,UPS面板电池电压红色LED指示灯长亮且蜂呜器长呜.现象分析与故障排除:根据上述故障现象可知,因蓄电池电压低于最低额定值,从而导致UPS启动不成功.打开UPS机箱,测量每节蓄电池两端电压,其值都几乎为0,说明蓄电池放电过多,导致UPS启动不成功.笔者试着用机械式万用表拔至电阻档的×1欧处,在开启UPS的同时用两支表笔迅速接触一下继电器S2的触发两端,结果UPS启发成功.在对UPS充电12小时后,再开UPS,故障现现象消失.从本例可知,因UPS的蓄电池过于放电,蓄电池的供电电压低于标称值(18V)太多,致使UPS启动不成功.故建议用户在对UPS的日常使用过程中,要对UPS的蓄电池定期的充一放电,否则电池的容量会减少,负载能力变差,重则报废.
Symptom: In the normal access to the case of electricity, each time you turn on the UPS, you will hear the relay “creak” repeated action sound, UPS panel battery voltage red LED indicator light and buzzer. And troubleshooting: According to the above symptoms, because the battery voltage is lower than the minimum rating, resulting in unsuccessful UPS startup. Open the UPS chassis, measuring the voltage across each battery, the value is almost 0, indicating excessive battery discharge , Resulting in UPS start unsuccessful.I tried to pull the mechanical multimeter to the resistance file × 1 ohm at the same time open the UPS with two test leads quickly touch the relay S2 trigger both ends of the results UPS inspired success in the UPS After 12 hours of charging, turn on the UPS, the fault phenomenon disappears from this example shows, because the UPS battery is too discharged, the battery supply voltage is lower than the nominal value (18V) too much, resulting in UPS start unsuccessful. UPS in the daily use of the process, the UPS battery to charge a regular charge and discharge, otherwise the battery capacity will be reduced, the load capacity worse, heavy scrapped.