论文部分内容阅读
摘要:表演艺术发展到今天,表现手段趋于多样化,舞台作为歌剧、舞剧、戏曲等项目的表演场合,仍然在表演艺术中占有首位位置。随着艺术的发展,对舞台灯光也提出了更高的要求。它要表现演出风格、形式的多样化,即能表现演出过程中灯光的快速切换,又能使灯光变化准确、细腻、流畅,具有完美的节奏感。演出灯光在观众视觉中,以不知不觉的方式进行光的明暗效果变化,形体空间变化。这就要求舞台灯光布局、选用灯具、灯光控制设备能塑造形象,渲染色彩,变化节奏,形成在视觉语汇的特有的舞台演出空间气氛,影响观众的情绪变化,构成演员、观众、情景混为一体的相互影响与舞台演出内容吻合的特定空间。本课题结合工程案例,对建筑电气专业如何根据规范与舞台工艺等专业公司的舞台灯光设计对接,进行探讨。
关键词:舞台灯光;技术控制;表演艺术
Abstract: Performing arts development today, performance means diversification, opera, ballet, opera stage as project performance situations, it still occupies first place in the performing arts. With the development of art, but also put forward higher requirements on the stage lights. This requires the stage lighting layout, selection of lamps, lighting control equipment can shape the image rendering, color, rhythm, form the performance space atmosphere in the special stage visual vocabulary, influence of emotional changes of specific audience, actors, the audience the scene space, mixed interaction and stage performance content for an agreement. Combined with the engineering example, the construction of electrical specialty according to the docking stage lighting design specification and stage technology professional company was discussed.
Key words: stage lighting; control technology; performing arts
中图分类号:TM923.53 文献标识码:A文章编号:
一、 工程概况
J大剧院兼会议中心,1500座位规模的大剧院及300座位剧院式会议厅兼报告厅,既可作为剧院场所,又可各种规模会议使用。建筑包括局部地下1层, 地上5 层(包括夹层为6层),建筑面积为22977 m2,建筑高度为23.9m(不含舞台上空部分)。主体结构耐久年限50年以上,为甲等剧场。其中1500座位规模大剧院的舞台装置由三部分组成,包括460m2的主(前)舞台、300m2的后舞台及左、右两个各300m2的侧舞台。本设计依据的主要规范为JGJ 57-2000《剧场建筑设计规范》、GB 50052-2009《供配电系统设计规范》、JGJ 16-2008《民用建筑电气设计规范》和GB 50016-2006《建筑设计防火规范》。
本工程舞台照明按一级负荷设计。本工程在地下一层设置变配电所,采用两路10kV电源同时工作,分列运行,互为备用。根据JGJ 16-2008第9.6.7条第2款规定,为了防止供电电源对舞台的电声、电视转播设备产生干扰,影响其正常运行,要求电声、电视转播设备的电源不宜接在舞台照明变压器上,即舞台照明和舞台音响分别由不同的变压器供电。专设两台1600kVA变压器分别为舞台照明及舞台机械电力设备等负荷供电,另外两台1600kVA变压器为其它照明、动力、空调、舞台音响等负荷供电。舞台机械、舞台照明及舞台音响等重要负荷的供电采用两路电源末端切换,以保证重要负荷的供电安全可靠。为有效抑制谐波,在变配电所供舞台机械、舞台照明及舞台音响的配电干线上,设置有源滤波装置。
二、 舞台照明系统
2. 1 舞台照明系统设计
J大剧院兼会议中心作为现代化的高层次表演场所,能适应多种舞台形式的演出需要,同时能够满足电视台现场直播的拍摄要求。作为国内一流剧场,整体系统配置既要满足现代剧场要求,又考虑扩充余量,并要求有合理的性能价格化,保证剧场在相当长时间内不会落伍,满足各类演出团体的使用要求。大剧院的主要使用功能是:举行各种大型会议、歌剧、舞剧、交响音乐会和大型综艺演出,因此舞台灯光照明系统的设计应满足以上使用功能的需要。系统要安全可靠、先进,主要设备选用国际先进产品;灯光回路设计中突出建设的超前意识,充分考虑舞台灯光的回路数,以满足现代艺术对舞台灯光灵活多变的要求;系统采用网络技术,有远程监控、反馈功能,系统有充分的扩展余地,并确定运行安全。舞台灯光照明系统设计要符合演出管理的要求。
2. 2 舞台照明主要设计指标
根据JGJ 16-2008第9.6.1、9.6.2条第规定,舞台照明每一回路的可载容量,应与所选用的调光设备的回路输出容量相适应。舞台照明调光回路数量,应根据剧场等级、规模确定。调光回路的功率一般是4~6KW,而且从安全角度考虑,一般4KW回路带2KW灯具,6KW回路带4KW灯具,均留有一定的裕度。关于舞台照明灯光照明回路分配数量,不同剧场、剧种均有其不同要求,尚未有统一的标准。而且舞台照明发展趋向于对回路多灯位,这样可适应舞台照明多功能的需求。舞台灯光回路的设计是一个大剧院舞台灯光设计的重点,因为好的设计可以在演出时为灯光创作人员提供艺术创作的空间和灵活用光的技术支持,因此要合理、科学的分配,避免回路的闲置问题。
舞台照明设计指标如下:
a. 调光回路:746 回路、5.5kW /回路,输出功率可设定。
b. 直放回路:170 回路、5.5kW /回路。
c. 场灯:5.5kW×20 回路,输出功率可设定。
d. 工作灯:5.5 kW×24 回路,输出功率可设定。
e. 调光台可控2048回路。
f. 照度标准:舞台平均照度不低于1200lx,表演区内任意位置有不少于3个方向的光,每一方向光的最大白光照度(单灯效果)不低于1000 lx;会议时,主席台的平均照度不低于300lx。
g. 显色指数:Ra > 92。
h.色温:常规灯具3200K,追光灯5600K。
i.调光柜抗干扰指标:达到或超过国家标准《电子调光设备无线电骚扰特性限值及测量方法》
中规定的一级机标准。
j.Ethernet 接口76 个,DMX512 接口117个。
2. 3 大剧院的灯位布置
随着舞台艺术的发展,对舞台灯光也提出了更高的要求。舞台灯光是舞台艺术的灵魂,完美的灯光配置和应用,是成功演出的必要条件。舞台灯光,概括起来,需从四个方面突出特点:写意、写实、美感、表现。大剧院为典型镜框式舞台,镜框式舞台的照明系统分镜框外照明系统和镜框内照明系统。镜框外照明系统包括面光、左右外侧光、台唇脚光。镜框内照明系统包括内侧光照明系统、顶光照明系统、天幕照明系统。
2. 4 大剧院舞台照明的控制
舞台照明总装机容量为5280kW。舞台灯光的使用多少根据不同剧目确定。实际使用最大可能是多少,这是很难确定的。有些演出团体根据需要自带灯具,此部分容量无法确定,还会出现负荷分配不均匀,导致中性线上不平衡电流较大。本工程设计中参考了国内同等规模的剧院设计,如新近建成的1800座位的上海大剧院,舞台灯光的总装机容量为2835KW,需要系数取0.5左右。并根据规范JGJ 16 - 2008表9. 6. 8的规定,与业主、舞台照明设计方多次沟通,仔细分析可能同时使用的灯具数量,舞台照明负荷需要系数取0.2,裕量系數取1.2,则舞台照明的计算容量为1267kW。还有待于今后实际使用中积累数据,加以证实。
舞台照明设备控制室与舞台机械设备控制室共用。内设电源配电柜5台,可控硅调光柜10台,网络柜1台。使调光柜引至各灯的线路尽可能短,减少压降损失。舞台灯光控制台设置在观众厅后部的灯控室内(标高6.10 m),方便操作人员对舞台灯光及观众厅内的场面进行观察。
大剧院舞台灯光控制系统演出前能将所有排换场所所需灯光设计编排成电脑程序,在演出时,能按需要用电脑做全场的灯光变化操作。并能对不同剧团的各种节目的灯光变化需要,记忆在电脑中,随时可以重复使用。。
结语
总之,剧院舞台灯光的设计有许多新技术需要我们不断学习和应用,以满足现代艺术对舞台灯光灵活多变的要求,形成在视觉语汇的特有的舞台演出空间气氛。
关键词:舞台灯光;技术控制;表演艺术
Abstract: Performing arts development today, performance means diversification, opera, ballet, opera stage as project performance situations, it still occupies first place in the performing arts. With the development of art, but also put forward higher requirements on the stage lights. This requires the stage lighting layout, selection of lamps, lighting control equipment can shape the image rendering, color, rhythm, form the performance space atmosphere in the special stage visual vocabulary, influence of emotional changes of specific audience, actors, the audience the scene space, mixed interaction and stage performance content for an agreement. Combined with the engineering example, the construction of electrical specialty according to the docking stage lighting design specification and stage technology professional company was discussed.
Key words: stage lighting; control technology; performing arts
中图分类号:TM923.53 文献标识码:A文章编号:
一、 工程概况
J大剧院兼会议中心,1500座位规模的大剧院及300座位剧院式会议厅兼报告厅,既可作为剧院场所,又可各种规模会议使用。建筑包括局部地下1层, 地上5 层(包括夹层为6层),建筑面积为22977 m2,建筑高度为23.9m(不含舞台上空部分)。主体结构耐久年限50年以上,为甲等剧场。其中1500座位规模大剧院的舞台装置由三部分组成,包括460m2的主(前)舞台、300m2的后舞台及左、右两个各300m2的侧舞台。本设计依据的主要规范为JGJ 57-2000《剧场建筑设计规范》、GB 50052-2009《供配电系统设计规范》、JGJ 16-2008《民用建筑电气设计规范》和GB 50016-2006《建筑设计防火规范》。
本工程舞台照明按一级负荷设计。本工程在地下一层设置变配电所,采用两路10kV电源同时工作,分列运行,互为备用。根据JGJ 16-2008第9.6.7条第2款规定,为了防止供电电源对舞台的电声、电视转播设备产生干扰,影响其正常运行,要求电声、电视转播设备的电源不宜接在舞台照明变压器上,即舞台照明和舞台音响分别由不同的变压器供电。专设两台1600kVA变压器分别为舞台照明及舞台机械电力设备等负荷供电,另外两台1600kVA变压器为其它照明、动力、空调、舞台音响等负荷供电。舞台机械、舞台照明及舞台音响等重要负荷的供电采用两路电源末端切换,以保证重要负荷的供电安全可靠。为有效抑制谐波,在变配电所供舞台机械、舞台照明及舞台音响的配电干线上,设置有源滤波装置。
二、 舞台照明系统
2. 1 舞台照明系统设计
J大剧院兼会议中心作为现代化的高层次表演场所,能适应多种舞台形式的演出需要,同时能够满足电视台现场直播的拍摄要求。作为国内一流剧场,整体系统配置既要满足现代剧场要求,又考虑扩充余量,并要求有合理的性能价格化,保证剧场在相当长时间内不会落伍,满足各类演出团体的使用要求。大剧院的主要使用功能是:举行各种大型会议、歌剧、舞剧、交响音乐会和大型综艺演出,因此舞台灯光照明系统的设计应满足以上使用功能的需要。系统要安全可靠、先进,主要设备选用国际先进产品;灯光回路设计中突出建设的超前意识,充分考虑舞台灯光的回路数,以满足现代艺术对舞台灯光灵活多变的要求;系统采用网络技术,有远程监控、反馈功能,系统有充分的扩展余地,并确定运行安全。舞台灯光照明系统设计要符合演出管理的要求。
2. 2 舞台照明主要设计指标
根据JGJ 16-2008第9.6.1、9.6.2条第规定,舞台照明每一回路的可载容量,应与所选用的调光设备的回路输出容量相适应。舞台照明调光回路数量,应根据剧场等级、规模确定。调光回路的功率一般是4~6KW,而且从安全角度考虑,一般4KW回路带2KW灯具,6KW回路带4KW灯具,均留有一定的裕度。关于舞台照明灯光照明回路分配数量,不同剧场、剧种均有其不同要求,尚未有统一的标准。而且舞台照明发展趋向于对回路多灯位,这样可适应舞台照明多功能的需求。舞台灯光回路的设计是一个大剧院舞台灯光设计的重点,因为好的设计可以在演出时为灯光创作人员提供艺术创作的空间和灵活用光的技术支持,因此要合理、科学的分配,避免回路的闲置问题。
舞台照明设计指标如下:
a. 调光回路:746 回路、5.5kW /回路,输出功率可设定。
b. 直放回路:170 回路、5.5kW /回路。
c. 场灯:5.5kW×20 回路,输出功率可设定。
d. 工作灯:5.5 kW×24 回路,输出功率可设定。
e. 调光台可控2048回路。
f. 照度标准:舞台平均照度不低于1200lx,表演区内任意位置有不少于3个方向的光,每一方向光的最大白光照度(单灯效果)不低于1000 lx;会议时,主席台的平均照度不低于300lx。
g. 显色指数:Ra > 92。
h.色温:常规灯具3200K,追光灯5600K。
i.调光柜抗干扰指标:达到或超过国家标准《电子调光设备无线电骚扰特性限值及测量方法》
中规定的一级机标准。
j.Ethernet 接口76 个,DMX512 接口117个。
2. 3 大剧院的灯位布置
随着舞台艺术的发展,对舞台灯光也提出了更高的要求。舞台灯光是舞台艺术的灵魂,完美的灯光配置和应用,是成功演出的必要条件。舞台灯光,概括起来,需从四个方面突出特点:写意、写实、美感、表现。大剧院为典型镜框式舞台,镜框式舞台的照明系统分镜框外照明系统和镜框内照明系统。镜框外照明系统包括面光、左右外侧光、台唇脚光。镜框内照明系统包括内侧光照明系统、顶光照明系统、天幕照明系统。
2. 4 大剧院舞台照明的控制
舞台照明总装机容量为5280kW。舞台灯光的使用多少根据不同剧目确定。实际使用最大可能是多少,这是很难确定的。有些演出团体根据需要自带灯具,此部分容量无法确定,还会出现负荷分配不均匀,导致中性线上不平衡电流较大。本工程设计中参考了国内同等规模的剧院设计,如新近建成的1800座位的上海大剧院,舞台灯光的总装机容量为2835KW,需要系数取0.5左右。并根据规范JGJ 16 - 2008表9. 6. 8的规定,与业主、舞台照明设计方多次沟通,仔细分析可能同时使用的灯具数量,舞台照明负荷需要系数取0.2,裕量系數取1.2,则舞台照明的计算容量为1267kW。还有待于今后实际使用中积累数据,加以证实。
舞台照明设备控制室与舞台机械设备控制室共用。内设电源配电柜5台,可控硅调光柜10台,网络柜1台。使调光柜引至各灯的线路尽可能短,减少压降损失。舞台灯光控制台设置在观众厅后部的灯控室内(标高6.10 m),方便操作人员对舞台灯光及观众厅内的场面进行观察。
大剧院舞台灯光控制系统演出前能将所有排换场所所需灯光设计编排成电脑程序,在演出时,能按需要用电脑做全场的灯光变化操作。并能对不同剧团的各种节目的灯光变化需要,记忆在电脑中,随时可以重复使用。。
结语
总之,剧院舞台灯光的设计有许多新技术需要我们不断学习和应用,以满足现代艺术对舞台灯光灵活多变的要求,形成在视觉语汇的特有的舞台演出空间气氛。