目的分析研究100级层流手术室较10000~100000级层流手术室空气质量动态变化对人工关节置换术后感染的预防影响。方法 180例行人工关节置换术治疗的患者,随机分为A组和B组,每组90例。A组用100级层流手术室,B组用10000~100000级层流手术室。通过对动、静状态下的沉降菌落数量的检测及术后患者感染率分析手术室空气质量变化对人工关节置换术后的感染预防影响。结果 A组静态沉降菌数量为(0.149±0.281)个,动态沉降菌数量为(24.685±12.628)个,低于B组的(0.661±0.904)、(42.794±18.560)个,差异有统计学意义(P<0.05)。A组术后感染发生率为3.33%,明显低于B组的27.78%(P<0.05)。结论手术室空气质量清洁度与关节置换术后感染紧密关联,改善和提高手术室环境水平有利于预防患者术后感染的发生。
Objective To analyze the preventive effect of dynamic changes of air quality in laminar flow operation room of 100-100 laminar flow operation rooms on the infection after artificial joint replacement. Methods 180 patients undergoing artificial joint replacement were randomly divided into A group and B group, 90 cases in each group. A group with 100 laminar flow operating room, B group with 10000 to 100000 laminar flow operating room. Through the detection of the number of the settled colonies in the static state and the postoperative infection rate, the change of the air quality in the operating room was analyzed to prevent the infection after artificial joint replacement. Results The number of static sedimentation in group A was (0.149 ± 0.281) and the number of dynamic sedimentation was (24.685 ± 12.628), which was lower than that in group B (0.661 ± 0.904) and (42.794 ± 18.560), respectively, with significant difference (P <0.05). The incidence of postoperative infection in group A was 3.33%, which was significantly lower than that in group B (27.78%, P <0.05). Conclusion The cleanliness of the air quality in the operating room is closely related to the infection after the joint replacement. Improving and improving the operating room environment is conducive to the prevention of postoperative infection.