摘要:随着高层建筑数量越来越多,高层建筑消防给排水系统是高层建筑设计中消防设计的基本组织成部分,其安全可靠性直接影响到消防灭火安全。消火栓系统在我国被称为最基本的灭火设备,每栋高层建筑都必须设置高层公共建筑,消火栓系统分为室外消火栓系统和室内消火栓系统,另外消防水源是保证消防系统工作的必要条件,其重要性显而易见。所以本文先探讨了高层建筑消火栓系统的含义、计算内容以及室外消火栓系统的形式和要求,然后根据工程实例并着重分析了室内消防给水系统如何设计,以供参考。
关键词:高层建筑消火栓系统;室外消火栓的设置;室内消防给水系统
Abstract: with more high-rise buildings, high building fire water supply and drainage system is in designing high-rise buildings fire design basic organized into its part, safety reliability directly affect the fire extinguishing security. Fire hydrant system in China is called the most basic fire extinguishing equipment, each high-rise building must be set top public building, fire hydrant system is divided into outdoor fire hydrant system and indoor fire hydrant system, another fire water supply is to ensure that the necessary conditions of fire protection system work, its importance is obvious. This paper first discusses the so high building fire hydrant system, calculation of the meaning of the content and the form of outdoor fire hydrant system and requirement, and then based on the engineering example and focuses on analyzing the fire water system indoor how to design, for reference.
Keywords: high building fire hydrant system; The setting of the outdoor fire cock; Indoor fire water system
中图分类号:TU998.1文献标识码:A文章编号:
引言
高层建筑消火栓系统是指高度较大(50m以上),会采用高低区分区供水,否则因为楼层高了水泵扬程很大则低区的管网压力会过大,一般分区共用水箱,底部供水环网可分别设立高低区供水环网,高区环网向低区环网加减压阀供水(低区环网压力变小),如楼层过高和高低区压差过大,水泵接合器也最好分高低区分别设置。
1.消火栓灭火系统工程量计算
一般包括以下内容,可能有的项目不一定用到:室内外管道安装(m),包括钢管的沟槽连接;阀门安装(个);报警装置安装(组);减压孔板安装(个);管道支架制作安装;室内外消火栓安装(套);消防水泵安装;消防水泵接合器安装(套);气压罐安装(台);管道支架刷油;管道刷油;管道绝热;套管的制作安装;系统强度试验;管道水冲洗;
2.室外消火栓的设置
室外消火栓的设置形式一般分为地上式与地下式两种,地上式显目,地下式防冻。
2.1室外消火栓应沿道路设置。
2.2甲、乙、丙类液体储罐区和液化石油气储罐区的消火栓应设置在防火堤或防护墙外。
2.3室外消火栓的间距不应大于120m;
2.4室外消火栓的保護半径不应大于150m;
2.5室外消火栓的数量应按其保护半径和室外消防用水量等综合计算确定,与保护对象的距离在5~40m 范围内的市政消火栓,可计入室外消火栓的数量内;
2.6室外消火栓宜采用地上式消火栓。寒冷地区设置的室外消火栓应有防冻措施;
2.7消火栓距路边不应大于2m,距房屋外墙不宜小于5m;
2.8工艺装置区内的消火栓应设置在工艺装置的周围,其间距不宜大于60m。当工艺装置区宽度大于120m 时,宜在该装置区内的道路边设置消火栓。
3.工程案例
有一块1公顷左右的地皮,开发商在此地皮上只建一座商住楼(20层4单元,底层为租赁商铺),剩余地皮主要是绿化,道路。本地皮比较偏远,无法接市政给水管网,周围也没有市政的消火栓。
3.1在这种情况下室外低压消火栓给水的流量取决于火场上所出水枪的数量。每个低压消火栓一般只供一辆消防车出水,常出2支口径为19mm的直流水枪,火场要求水枪充实水柱为10―15m,则每支水枪的流量为5―6.5L/S,2支水枪的流量为10―13L/S,考虑接口及水带的漏水,所以每个低压消火栓的流量按10―15L/S计。每个室外高压消火栓给水一般按出口径为19mm的直流水枪考虑,水枪充实水柱为10―15m,则要求每个高压消火栓的流量不小于5L/S。室外消火栓,北方一般都是地下的,有井盖;南方是地上的,红色的长的,有几个接口的在路边上和市政管网相连的消火栓。室外消火栓的间距不得超过120米。室外消火栓的保护半径不得超过150米。室外消火栓距路边距离不得超过2米,与房屋外墙距离不宜小于5米。
4.以上所说的是室外消火栓的情况,下面是室内消火栓的情况即室内消防给水系统。
4.1室内消防给水系统应与生活、生产给水系统分开独立设置。室内消防给水管道应布置成环状。室内消防给水环状管网的进水管和区域高压或临时高压给水系统的引入管不应少于两根,当其中一根发生故障时,其余的进水管或引入管应能保证消防用水量和水压的要求。
4.1.1消防竖管的布置,应保证同层相邻两个消火栓的水枪的充实水柱同时达到被保护范围内的任何部位。每根消防竖管的直径应按通过的流量经计算确定,但不应小于100mm。
以下情况,当设两根消防竖管有困难时,可设一根竖管,但必须采用双阀双出口型消火栓。
(1)十八层及十八层以下的单元式住宅;
(2)十八层及十八层以下、每层不超过8户、建筑面积不超过650m2的塔式住宅。
4.1.2用消防泵,但在自动喷水灭火系统的报警阀前(沿水流方向)必须分开设置。
4.1.3室内消防给水管道应采用阀门分成若干独立段。阀门的布置,应保证检修管道时关闭停用的竖管不超过一根。当竖管超过4根时,可关闭不相邻的两根。裙房内消防给水管道的阀门布置可按现行的国家标准《建筑设计防火规范》的有关规定执行。阀门应有明显的启闭标志。
4.2室内消火栓给水系统和自动喷水灭火系统应设水泵接合器,并应符合下列规定:
(1)水泵接合器的数量应按室内消防用水量经计算确定。每个水泵接合器的流量应按10~15L/s计算。
(2)消防给水为竖向分区供水时,在消防车供水压力范围内的分区,应分别设置水泵接合器。
(3)水泵接合器应设在室外便于消防车使用的地点,距室外消火栓或消防水池的距离宜为15~40m。
(4)水泵接合器宜采用地上式;当采用地下式水泵接合器时,应有明显标志。
4.3除无可燃物的设备层外,高层建筑和裙房的各层均应设室内消火栓,并应符合下列规定:
(1)消火栓应设在走道、楼梯附近等明显易于取用的地点,消火栓的间距应保证同层任何部位有两个消火栓的水枪充实水柱同时到达。
(2)消火栓的水枪充实水柱应通过水力计算确定,且建筑高度不超过100m的高层建筑不应小于10m;建筑高度超过100m的高层建筑不应小于13m。
(3)消火栓的间距应由计算确定,且高层建筑不应大于30m,裙房不应大于50m。
(4)消火栓栓口离地面高度宜为1.10m,栓口出水方向宜向下或与设置消火栓的墙面相垂直。
(5)消火栓栓口的静水压力不应大于1.00MPa,当大于1.00MPa时,应采取分区给水系统。消火栓栓口的出水压力大于0.50MPa时,应采取减压措施。
(6)消火栓应采用同一型号规格。消火栓的栓口直径应为65mm,水带长度不应超过25m,水枪喷嘴口径不应小于19mm。
(7)临时高压给水系统的每个消火栓处应设直接启动消防水泵的按钮,并应设有保护按钮的设施。
(8)消防电梯间前室应设消火栓。
(9)高层建筑的屋顶应设一个装有压力显示装置的检查用的消火栓,采暖地区可设在顶层出口处或水箱间内。
4.4采用高压给水系统时,可不设高位消防水箱。当采用临时高压给水系统时,应设高位消防水箱,并应符合下列规定:
(1)高位消防水箱的消防储水量,一类公共建筑不应小于18m3;二类公共建筑和一类居住建筑不应小于12m3;二类居住建筑不应小于6.00m3。
(2)高位消防水箱的设置高度应保证最不利点消火栓静水压力。当建筑高度不超过100m时,高层建筑最不利点消火栓静水压力不应低于0.07MPa;当建筑高度超过100m时,高层建筑最不利点消火栓静水压力不应低于0.15MPa。当高位消防水箱不能满足上述静压要求时,应设增压设施。
(3)并联给水方式的分区消防水箱容量应与高位消防水箱相同。
(4)消防用水与其它用水合用的水箱,应采取确保消防用水不作他用的技术措施。
(5)除串联消防给水系统外,发生火灾时由消防水泵供给的消防用水不应进入高位消防水箱。
4.5设有高位消防水箱的消防给水系统,其增压设施应符合下列规定:
(1)增压水泵的出水量,对消火栓给水系统不应大于5L/s;对自动喷水灭火系统不应大于1L/s。
(2)气压水罐的调节水容量宜为450L。
4.6消防卷盤的间距应保证有一股水流能到达室内地面任何部位,消防卷盘的安装高度应便于取用。
注:消防卷盘的栓口直径宜为25mm;配备的胶带内径不小于19mm;消防卷盘喷嘴口径不小于6.00mm。
结论:
高层建筑的防火栓系统的设计,必须遵循“预防为主,防消结合”的消防工作方针,针对高层建筑发生火灾的特点,立足自防自救,采用可靠的防火措施,做到安全适用、技术先进、经济合理。
关键词:高层建筑消火栓系统;室外消火栓的设置;室内消防给水系统
Abstract: with more high-rise buildings, high building fire water supply and drainage system is in designing high-rise buildings fire design basic organized into its part, safety reliability directly affect the fire extinguishing security. Fire hydrant system in China is called the most basic fire extinguishing equipment, each high-rise building must be set top public building, fire hydrant system is divided into outdoor fire hydrant system and indoor fire hydrant system, another fire water supply is to ensure that the necessary conditions of fire protection system work, its importance is obvious. This paper first discusses the so high building fire hydrant system, calculation of the meaning of the content and the form of outdoor fire hydrant system and requirement, and then based on the engineering example and focuses on analyzing the fire water system indoor how to design, for reference.
Keywords: high building fire hydrant system; The setting of the outdoor fire cock; Indoor fire water system
中图分类号:TU998.1文献标识码:A文章编号:
引言
高层建筑消火栓系统是指高度较大(50m以上),会采用高低区分区供水,否则因为楼层高了水泵扬程很大则低区的管网压力会过大,一般分区共用水箱,底部供水环网可分别设立高低区供水环网,高区环网向低区环网加减压阀供水(低区环网压力变小),如楼层过高和高低区压差过大,水泵接合器也最好分高低区分别设置。
1.消火栓灭火系统工程量计算
一般包括以下内容,可能有的项目不一定用到:室内外管道安装(m),包括钢管的沟槽连接;阀门安装(个);报警装置安装(组);减压孔板安装(个);管道支架制作安装;室内外消火栓安装(套);消防水泵安装;消防水泵接合器安装(套);气压罐安装(台);管道支架刷油;管道刷油;管道绝热;套管的制作安装;系统强度试验;管道水冲洗;
2.室外消火栓的设置
室外消火栓的设置形式一般分为地上式与地下式两种,地上式显目,地下式防冻。
2.1室外消火栓应沿道路设置。
2.2甲、乙、丙类液体储罐区和液化石油气储罐区的消火栓应设置在防火堤或防护墙外。
2.3室外消火栓的间距不应大于120m;
2.4室外消火栓的保護半径不应大于150m;
2.5室外消火栓的数量应按其保护半径和室外消防用水量等综合计算确定,与保护对象的距离在5~40m 范围内的市政消火栓,可计入室外消火栓的数量内;
2.6室外消火栓宜采用地上式消火栓。寒冷地区设置的室外消火栓应有防冻措施;
2.7消火栓距路边不应大于2m,距房屋外墙不宜小于5m;
2.8工艺装置区内的消火栓应设置在工艺装置的周围,其间距不宜大于60m。当工艺装置区宽度大于120m 时,宜在该装置区内的道路边设置消火栓。
3.工程案例
有一块1公顷左右的地皮,开发商在此地皮上只建一座商住楼(20层4单元,底层为租赁商铺),剩余地皮主要是绿化,道路。本地皮比较偏远,无法接市政给水管网,周围也没有市政的消火栓。
3.1在这种情况下室外低压消火栓给水的流量取决于火场上所出水枪的数量。每个低压消火栓一般只供一辆消防车出水,常出2支口径为19mm的直流水枪,火场要求水枪充实水柱为10―15m,则每支水枪的流量为5―6.5L/S,2支水枪的流量为10―13L/S,考虑接口及水带的漏水,所以每个低压消火栓的流量按10―15L/S计。每个室外高压消火栓给水一般按出口径为19mm的直流水枪考虑,水枪充实水柱为10―15m,则要求每个高压消火栓的流量不小于5L/S。室外消火栓,北方一般都是地下的,有井盖;南方是地上的,红色的长的,有几个接口的在路边上和市政管网相连的消火栓。室外消火栓的间距不得超过120米。室外消火栓的保护半径不得超过150米。室外消火栓距路边距离不得超过2米,与房屋外墙距离不宜小于5米。
4.以上所说的是室外消火栓的情况,下面是室内消火栓的情况即室内消防给水系统。
4.1室内消防给水系统应与生活、生产给水系统分开独立设置。室内消防给水管道应布置成环状。室内消防给水环状管网的进水管和区域高压或临时高压给水系统的引入管不应少于两根,当其中一根发生故障时,其余的进水管或引入管应能保证消防用水量和水压的要求。
4.1.1消防竖管的布置,应保证同层相邻两个消火栓的水枪的充实水柱同时达到被保护范围内的任何部位。每根消防竖管的直径应按通过的流量经计算确定,但不应小于100mm。
以下情况,当设两根消防竖管有困难时,可设一根竖管,但必须采用双阀双出口型消火栓。
(1)十八层及十八层以下的单元式住宅;
(2)十八层及十八层以下、每层不超过8户、建筑面积不超过650m2的塔式住宅。
4.1.2用消防泵,但在自动喷水灭火系统的报警阀前(沿水流方向)必须分开设置。
4.1.3室内消防给水管道应采用阀门分成若干独立段。阀门的布置,应保证检修管道时关闭停用的竖管不超过一根。当竖管超过4根时,可关闭不相邻的两根。裙房内消防给水管道的阀门布置可按现行的国家标准《建筑设计防火规范》的有关规定执行。阀门应有明显的启闭标志。
4.2室内消火栓给水系统和自动喷水灭火系统应设水泵接合器,并应符合下列规定:
(1)水泵接合器的数量应按室内消防用水量经计算确定。每个水泵接合器的流量应按10~15L/s计算。
(2)消防给水为竖向分区供水时,在消防车供水压力范围内的分区,应分别设置水泵接合器。
(3)水泵接合器应设在室外便于消防车使用的地点,距室外消火栓或消防水池的距离宜为15~40m。
(4)水泵接合器宜采用地上式;当采用地下式水泵接合器时,应有明显标志。
4.3除无可燃物的设备层外,高层建筑和裙房的各层均应设室内消火栓,并应符合下列规定:
(1)消火栓应设在走道、楼梯附近等明显易于取用的地点,消火栓的间距应保证同层任何部位有两个消火栓的水枪充实水柱同时到达。
(2)消火栓的水枪充实水柱应通过水力计算确定,且建筑高度不超过100m的高层建筑不应小于10m;建筑高度超过100m的高层建筑不应小于13m。
(3)消火栓的间距应由计算确定,且高层建筑不应大于30m,裙房不应大于50m。
(4)消火栓栓口离地面高度宜为1.10m,栓口出水方向宜向下或与设置消火栓的墙面相垂直。
(5)消火栓栓口的静水压力不应大于1.00MPa,当大于1.00MPa时,应采取分区给水系统。消火栓栓口的出水压力大于0.50MPa时,应采取减压措施。
(6)消火栓应采用同一型号规格。消火栓的栓口直径应为65mm,水带长度不应超过25m,水枪喷嘴口径不应小于19mm。
(7)临时高压给水系统的每个消火栓处应设直接启动消防水泵的按钮,并应设有保护按钮的设施。
(8)消防电梯间前室应设消火栓。
(9)高层建筑的屋顶应设一个装有压力显示装置的检查用的消火栓,采暖地区可设在顶层出口处或水箱间内。
4.4采用高压给水系统时,可不设高位消防水箱。当采用临时高压给水系统时,应设高位消防水箱,并应符合下列规定:
(1)高位消防水箱的消防储水量,一类公共建筑不应小于18m3;二类公共建筑和一类居住建筑不应小于12m3;二类居住建筑不应小于6.00m3。
(2)高位消防水箱的设置高度应保证最不利点消火栓静水压力。当建筑高度不超过100m时,高层建筑最不利点消火栓静水压力不应低于0.07MPa;当建筑高度超过100m时,高层建筑最不利点消火栓静水压力不应低于0.15MPa。当高位消防水箱不能满足上述静压要求时,应设增压设施。
(3)并联给水方式的分区消防水箱容量应与高位消防水箱相同。
(4)消防用水与其它用水合用的水箱,应采取确保消防用水不作他用的技术措施。
(5)除串联消防给水系统外,发生火灾时由消防水泵供给的消防用水不应进入高位消防水箱。
4.5设有高位消防水箱的消防给水系统,其增压设施应符合下列规定:
(1)增压水泵的出水量,对消火栓给水系统不应大于5L/s;对自动喷水灭火系统不应大于1L/s。
(2)气压水罐的调节水容量宜为450L。
4.6消防卷盤的间距应保证有一股水流能到达室内地面任何部位,消防卷盘的安装高度应便于取用。
注:消防卷盘的栓口直径宜为25mm;配备的胶带内径不小于19mm;消防卷盘喷嘴口径不小于6.00mm。
结论:
高层建筑的防火栓系统的设计,必须遵循“预防为主,防消结合”的消防工作方针,针对高层建筑发生火灾的特点,立足自防自救,采用可靠的防火措施,做到安全适用、技术先进、经济合理。